Circulating Air & Filters; Duct Work - Air Flow; Checking Duct Static - Amana MSS9 Installation Instructions Manual

Single-stage gas furnace
Table of Contents

Advertisement

Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length
Feet
3/8"
1/2"
5/8"
10
730
1,700
3,200
20
500
1,100
220
30
400
920
2,000
40
370
850
1,700
50
330
770
1,500
60
300
700
1,300
80
260
610
1,200
100
220
540
1,000
125
200
490
900
150
190
430
830
175
170
400
780
200
160
380
730
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Propane Gas Piping Chart I
C
A
& F
IRCULATING
IR
D
- A
F
UCT WORK
IR
LOW
Duct systems and register sizes must be properly designed for the
CFM and external static pressure rating of the furnace. Design
the ductwork in accordance with the recommended methods of
"Air Conditioning Contractors of America" Manual D.
Install the duct system in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning,
Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the return duct connected to the furnace. NOTE: Ductwork must never be attached
to the back of the furnace. For upflow installations requiring 1800 CFM or more, use either two side returns or bottom return or a
combination of side /bottom. Flexible joints may be used for supply and return connections to reduce noise transmission. To prevent
the blower from interfering with combustion air or draft when a central return is used, a connecting duct must be installed between
the unit and the utility room wall. Never use a room, closet, or alcove as a return air chamber.
C
D
S
HECKING
UCT
TATIC
Refer to your furnace rating plate for the maximum ESP (external duct static) rating.
Total external static refers to everything external to the furnace cabinet. Cooling coils, filters, ducts, grilles, registers must
all be considered when reading your total external static pressure. The supply duct pressure must be read between the
furnace and the cooling coil. This reading is usually taken by removing the "A" shaped block off plate from the end on the
coil; drilling a test hole in it and reinstalling the block off plate. Take a duct static reading at the test hole. Tape up the test
hole after your test is complete. The negative pressure must be read between the filter and the furnace blower.
Too much external static pressure will result in insufficient air that can cause excessive temperature rise. This can cause
limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as follows;
1. With clean filters in the furnace, use a draft gauge (inclined manometer) to measure the static pressure of the return
duct at the inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive Pressure)
3. The difference between the two numbers is .4" w.c.
Nominal Pipe Size
Schedule 40
3/4"
7/8"
1/2"
5,300
8,300
3,200
3,700
5,800
2,200
2,900
4,700
1,800
2,700
4,100
1,600
2,400
3,700
1,500
2,200
3,300
1,300
1,900
2,900
1,200
1,700
2,600
1,000
1,400
2,300
900
1,300
2,100
830
1,200
1,900
770
1,100
1,800
720
ILTERS
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum Propane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pip e o r
Tu bin g
T ub ing S iz e, O .D. T yp e L
Len gt h
3/4"
F eet
3/8"
1/2"
7,500
10
39
92
4,200
20
26
62
4,000
30
21
50
3,700
40
19
41
3,400
50
18
37
3,100
60
16
35
2,600
80
13
29
2,300
100
11
26
2,100
125
10
24
1,900
150
9
21
1,700
200
8
19
1,500
250
8
17
*Data in ac cor danc e wit h NFP A pamphl et No. 54
N
EVER ALLOW THE PRODUCTS OF COMBUSTION
,
MONOXIDE
TO ENTER THE RETURN DUCT WORK OR CIRCULATION AIR
.
SUPPLY
29
Nom inal P ipe Siz e
5/8"
3/4"
7 /8"
1/2"
3/4"
199
3 29
501
275
567
131
2 16
346
189
393
107
1 81
277
152
315
90
1 45
233
129
267
79
1 31
198
114
237
72
1 21
187
103
217
62
1 04
155
89
185
55
9 0
138
78
162
48
8 1
122
69
146
43
7 2
109
63
132
39
6 6
100
54
112
36
6 0
93
48
100
Propane Gas Piping Chart II
WARNING
S chedu le 40
1"
1- 1/4" 1- 1/2"
1,07 1 2,205
3,307
732
1,496
2,299
590
1,212
1,858
504
1,039
1,559
448
913
1,417
409
834
1,275
346
724
1,066
307
630
976
275
567
866
252
511
787
209
439
665
185
390
590
,
INCLUDING CARBON