*MES80/*CES80
GAS FURNACE -
CATÉGORIE I
These furnaces comply with requirements embodied
in the American National Standard / National
Standard of Canada ANSI Z21.47·CSA-2.3 Gas
Fired Central Furnaces.
ATTENTION INSTALLING PERSONNEL
As a professional installer, you have an obligation to know
the product better than the customer. This includes all safety
precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with
this Instruction Manual. Pay special attention to all safety
warnings. Often during installation or repair, it is possible to
place yourself in a position which is more hazardous than
when the unit is in operation.
Remember, it is your responsibility to install the product safely
and to know it well enough to be able to instruct a customer
in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specific, good safety
practices...follow them.
The precautions listed in this Installation Manual are intended
as supplemental to existing practices. However, if there is a
direct conflict between existing practices and the content of
this manual, the precautions listed here take precedence.
R
ECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
NOTE: Please contact your distributor or our website listed
below for the applicable Specification Sheet referred to in
this manual.
PROP 65 WARNING
FOR CALIFORNIA CONSUMERS
Cancer and Reproductive Harm -
www.P65Warnings.ca.gov
IOG-2021D
03/2020
CATEGORY 1
0140M00517-A
www.goodmanmfg.com • www.amana-hac.com
© 2019 - 2020 Goodman Manufacturing Company, L.P.
® is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
Index
SAFETY CONSIDERATIONS............................................ 3
Additional Safety Considerations....................................... 4
Shipping Inspection........................................................... 4
To The Installer.................................................................. 5
PRODUCT APPLICATION................................................. 5
Clearances and Accessibility............................................. 7
Installation Positions.......................................................... 7
Horizontal Installation........................................................ 8
Furnace Suspension......................................................... 8
Existing Furnace Removal................................................ 8
Thermostat Location......................................................... 9
...........................................................................................9
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL
SERVICE OR REPAIR
SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT
MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR
PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE
. I
PROCEDURES
F YOU SERVICE THIS UNIT
RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY
. I
RESULT
N ADDITION
MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
,
MANUAL
ONLY LICENSED PERSONNEL SHOULD SERVICE THE
. I
EQUIPMENT
MPROPER INSTALLATION
REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL
ATTEMPTING TO INSTALL
EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING
MAY RESULT IN PRODUCT DAMAGE
.
INJURY OR DEATH
19001 Kermier Rd.
Waller, TX 77484
Installer: Affix all manuals
adjacent to the unit.
(
, "
")
HEREINAFTER
SERVICE
THE EQUIPMENT
,
YOU ASSUME
,
IN JURISDICTIONS THAT REQUIRE ONE OR
,
ADJUSTMENT
,
,
ADJUST
SERVICE OR REPAIR THE
,
PROPERTY DAMAGE
,
,
ADJUST
. T
HE
,
SERVICING OR
,
OR
,
PERSONAL

Advertisement

Table of Contents
loading

Summary of Contents for Amana MES80

  • Page 1: Table Of Contents

    INJURY OR DEATH 19001 Kermier Rd. Waller, TX 77484 IOG-2021D www.goodmanmfg.com • www.amana-hac.com 03/2020 © 2019 - 2020 Goodman Manufacturing Company, L.P. ® is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
  • Page 2 MASONRY CHIMNEYS ............11 Igniter (Qualified Servicer Only)........24 Masonry Chimney Termination..........11 Burners................24 ELECTRICAL CONNECTIONS........11 CLEANING (QUALIFIED SERVICER ONLY)....24 Wiring Harness..............12 BEFORE LEAVING AN INSTALLATION......25 115 Volt Line Connections..........12 REPAIR AND REPLACEMENT PARTS......25 Fossil Fuel Applications........... 12 Component ID..............
  • Page 3: Safety Considerations

    Safety Considerations WARNING Adhere to the following warnings and cautions when installing, O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER adjusting, altering, servicing, or operating the furnace. INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE ensure proper installation and operation, thoroughly read REFER TO THIS MANUAL OR ADDITIONAL ASSISTANCE OR this manual for specifics pertaining to the installation and...
  • Page 4: Additional Safety Considerations

    RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio. Cette ventilation est nécessaire pour éviter le danger d'intoxication Las emisiones de monóxido de carbono pueden circular a través au CO pouvant survenir si un appareil produisant du monoxyde del aparato cuando se opera en cualquier modo.
  • Page 5: Electrostatic Discharge (Esd) Precautions

    Electrostatic Discharge (ESD) Precautions In such applications , the furnace must be installed with the following stipulations: NOTE: Discharge your body’s static electricity before touching • It must be installed per the installation instructions unit. An electrostatic discharge can adversely affect electrical provided and per local and national codes.
  • Page 6: Location Requirements And Considerations

    WARNING WARNING O PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO O PREVENT POSSIBLE EQUIPMENT DAMAGE PROPERTY DAMAGE FIRE DO NOT INSTALL THIS FURNACE IN A MOBILE HOME TRAILER PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE RECREATIONAL VEHICLE OBSERVED WHEN INSTALLING THIS UNIT Follow the instructions listed below when selecting a furnace...
  • Page 7: Clearances And Accessibility

    For vertical (upflow or downflow) applications, the Vent Pipe Clearance to Combustibles- 6" using Single Wall Connector or 1" minimum cooling coil width shall not be less than using B-1 vent. furnace width minus 1”. Additionally, a coil installed above an upflow furnace or under a counterflow Top - 1"...
  • Page 8: Horizontal Installation

    Horizontal Installation Existing Furnace Removal NOTE: When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances. WARNING ARBON ONOXIDE OISONING AZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
  • Page 9: Thermostat Location

    Thermostat Location AVERTISSEMENT In an area having good air circulation, locate the thermostat ISQUE NTOXICATION ONOXYDE DE ARBONE about five feet high on a vibration-free inside wall. Do not install the thermostat where it may be influenced by any of Si les ‫י‬tapes d‫י‬crites ci-dessous ne sont pas suivies pour chacun the following: •...
  • Page 10: Category I Venting (Vertical Venting)

    Category I Venting (Vertical Venting) Upflow or Horizontal units are shipped with the induced draft blower discharging from the top of the furnace. (“Top” is as viewed for an upflow installation.) The induced draft blower WARNING can be rotated 90 degrees with the (0270F01119) chimney O PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO transition bottom kit for Category I venting.
  • Page 11: Masonry Chimneys

    14. Restore power to furnace. WARNING NOTE: In a horizontal installation the air conditioning coil must be adequately supported by proper brackets and OSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH supports. Inadequate coil support can result in furnace DAMAGING CONDENSATION CAN OCCUR INSIDE MASONRY CHIMNEYS cabinet distortion and air leakage.
  • Page 12: Wiring Harness

    Junction Box Relocation WARNING WARNING HIGH VOLTAGE ! DGES OF SHEET METAL HOLES MAY BE SHARP SE GLOVES AS A O AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR PRECAUTION WHEN REMOVING HOLE PLUGS DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATEST EDITION OF THE...
  • Page 13: 24 Volt Thermostat Wiring

    To ensure proper unit grounding, the ground wire should run If it is necessary for the installer to supply additional line volt- from the furnace ground screw located inside the furnace age wiring to the inside of the furnace, the wiring must conform junction box all the way back to the electrical panel.
  • Page 14: Twinning

    Twinning input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the fur nace can result in premature heat exchanger failure. Gas pressures in excess Furnaces may be twinned without the use of a twinning of 13 inch es water column can also cause permanent damage kit.
  • Page 15: Gas Piping Connections

    TWINNING CONNECTION DIAGRAM 5240 5240 REV.0 REV.0 CR15 CR19 R175 CR19 CR15 R175 R177 R179 R177 R176 C28 R178 R179 R176 C28 R178 FLA ME FLA ME C U R R E N T C U R R E N T 1V DC=1UA 1V DC=1UA CR38...
  • Page 16: Upflow Installations

    • Install a drip leg to trap dirt and moisture before it can When the gas piping enters through the side of the furnace, enter the gas valve. The drip leg must be a minimum the installer must supply the following fittings starting from of three inches long.
  • Page 17: Propane Gas Tanks And Piping

    Propane Gas Tanks and Piping A duct system must be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of WARNING Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B. F THE GAS FURNACE IS INSTALLED IN A BASEMENT AN EXCAVATED AREA OR CONFINED SPACE...
  • Page 18: Sequence Of Operation

    • Induced draft blower is energized for 15 second pre- installed in the central return register or a side panel external purge period causing pressure switch contacts to close. filter rack kit (upflows), or the ductwork above a downflow furnace. As an alternative, a media air filter or electronic air •...
  • Page 19: Start-Up Procedure And Adjustment

    White-Rodgers valves : Push the switch to the ON • Circulator blower is energized on T1 speed. Electronic position. air cleaner terminals are energized. 8. Replace the door on the front of the furnace. • Circulator blower runs, integrated control module monitors safety circuits continuously.
  • Page 20: Gas Manifold Pressure Measurement And Adjustment

    Gas Valve On/Off INLET GAS SUPPLY PRESSURE Selector Inlet Pressure Natural Gas Minimum: 4.5" w.c. Maximum: 10.0" w.c. Switch Propane Gas Minimum: 11.0" w.c. Maximum: 13.0" w.c. INLET OUTLET Gas Line Shutoff Valve Pressure Regulator Outlet Pressure Adjustment (Under Cap Screw) Gas Line To Furnace White-Rodgers Model 36J22...
  • Page 21: Gas Input Rate Measurement (Natural Gas Only)

    6. Turn ON power and close thermostat “R” and “W” 5. Turn ON gas and relight appliances turned off in step contacts to provide a call for heat. 1. Ensure all the appliances are functioning properly 7. Using a leak detection solution or soap suds to check and that all pilot burners are operating.
  • Page 22: Circulator Blower Speed Adjustment

    Circulator Blower Speed Adjustment COOL MOTOR SPEED DIP SWITCH SETTING (S1-1, S1-2, S1-3) WARNING OFF OFF OFF ON OFF OFF Position O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK Motor Speed TURN POWER TO THE FURNACE BEFORE CHANGING SPEED TAPS COOL Furnaces are equipped with a EEM circulator blower motor.
  • Page 23: Burner Flame

    Excessive external static pressure will result in insufficient air that can cause excessive temperature rise. This can cause limit switch tripping and heat exchanger failure. To determine total external duct static pressure, proceed as follows; 1. With clean filters in the furnace, use a draft gauge (inclined manometer) to measure the static pressure of the return duct at the inlet of the furnace.
  • Page 24 59-5240 REV.003 CR35 CR18 R175 CR19 CR13 CR15 R177 R176 CR36 R179 R178 FLAME CURRENT 1VDC=1UA R181 CR38 R110 R112 CR37 R111 R113 R121 R115 R126 R125 R123 R120 R151 R180 R150 R145 R149 R168 R170 R148 CR26 R117 R118 R119 R122 R136...
  • Page 25: Primary Limit

    NOTE: If the condition which originally caused the lockout still Primary Limit exists, the control will return to lockout. Refer to the Diagnostic The primary limit control is located on the partition panel and Chart for aid in determining the cause. monitors heat exchanger compartment temperatures.
  • Page 26: Filter Removal

    Burners WARNING WARNING HIGH VOLTAGE! O PREVENT PERSONAL INJURY OR DEATH DO NOT REMOVE ANY O PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DISCONNECT INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT BEFORE LECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS ELECTRICAL POWER TO THE FURNACE REMOVING THE FILTER OR PERFORMING ANY OTHER ONTACT A QUALIFIED SERVICE AGENT AT ONCE IF AN ABNORMAL...
  • Page 27: Repair And Replacement Parts

    Repair and Replacement Parts • When ordering any of the listed functional parts, be sure to provide the furnace model, manufacturing, and serial numbers with the order. • Although only functional parts are shown in the parts list, all sheet metal parts, doors, etc. may be ordered by description.
  • Page 28: Component Id

    Component ID Tubular Heat Exchanger Pressure Switch Flue Pipe Connection Induced Draft Blower (Chimney Transition Top Shipped Loose) 躀 Gas Line Entrance Gas Valve Rollout Limit Junction Box Wiring Harness Grommet Gas Manifold Gas Line Entrance (Alternate) Inshot Burner Transformer Circulator Blower Blower Door Interlock Switch...
  • Page 29: Troubleshooting Chart

    Troubleshooting Chart PCBBF145 CONTROL BOARD Associated Symptoms of Abnormal Operation Fault Description(s) Possible Causes Corrective Action Cautions and Notes LED Code • Manual disconnect • Assure 115 and 24 volt • Turn power OFF • Furnace fails to operate. • No 115 volt power •...
  • Page 30 Troubleshooting Chart PCBBF145 CONTROL BOARD Associated Symptoms of Abnormal Operation Fault Description(s) Possible Causes Corrective Action Cautions and Notes LED Code • Circulator blower runs • Primary or auxiliary • Faulty primary or • Check primary/ • Turn power OFF prior continuously.
  • Page 31 Troubleshooting Chart PCBBF145 CONTROL BOARD Associated Symptoms of Abnormal Operation Fault Description(s) Possible Causes Corrective Action Cautions and Notes LED Code • Circulating blowers not •Twinning Fault • Furnace twin terminals • Install field wiring • Verify line voltage operating simultaneously. not connected together connecting twin supply is turned off...
  • Page 32: Blower Performance Data

    Blower Performance Data *CES80 Heating Airflow EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) DIP SWITCHES S2-1 , MODEL S2-2 RISE RISE RISE RISE RISE OFF OFF ON OFF* *CES 800403A* ON ON OFF ON** 1104 1058 1020 1022 1013 OFF OFF ON OFF* 1054 1002...
  • Page 33 Blower Performance Data *CES80 Cooling Airflow EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) DIP SWITCHES S1-1 , MODEL S1-2 , S1-3 OFF OFF OFF OFF ON ON ON OFF ON ON ON ON *CES 800403A* ON OFF OFF ON ON OFF 1104 1058 1020...
  • Page 34 Blower Performance Data *MES80 Heating Airflow EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) DIP SWITCHES S2-1 , MODEL S2-2 RISE RISE RISE RISE RISE OFF OFF ON OFF* *MES 800403A* ON ON OFF ON** 1138 1093 1057 1016 OFF OFF 1151...
  • Page 35 Blower Performance Data *MES80 Circulation Airflow EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) DIP SWITCHES S2-3 , MODEL S2-4 OFF OFF ON OFF *MES 800403A* OFF ON 1138 1093 1057 1016 1367 1321 1286 1255 1223 1190 1160 1133 1099 1068...
  • Page 36 Blower Performance Data *MES80 Cooling Airflow EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) DIP SWITCHES S1-1 , MODEL S1-2 , S1-3 OFF OFF OFF OFF ON ON ON OFF ON ON ON ON *MES 800403A* ON OFF OFF ON ON OFF...
  • Page 37 Blower Performance Data *MES80 COOLING AIRFLOW DATA EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) DIP SWITCHES S1-1 , MODEL S1-2 , S1-3 OFF OFF OFF OFF ON ON ON OFF ON ON ON ON *MES 800804B* ON OFF OFF 1408 1369...
  • Page 38 *MES80 / *CES80 Wiring Diagram WARNING:DISCONNECT POWER BEFORE SERVICING.WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. HUMIDIFIER INTEGRATED CONTROL MODULE GND (8) VALVE MVC (9) MV (12) ID BLOWER PRESSURE AUXILIARY SWITCH LIMIT CONTROLS PS (10) PSO (4) MICRO...
  • Page 39 THIS PAGE INTENTIONALLY LEFT BLANK...
  • Page 40 We are very interested in all product comments. Please fill out the feedback on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand AMANA® BRAND GOODMAN®...

This manual is also suitable for:

Ces80

Table of Contents