Gas Piping Checks; Propane Gas Tanks And Piping; Circulating Air & Filters; Duct Work - Air Flow - Amana M9S96 Series Installation Instructions Manual

Table of Contents

Advertisement

Gas Piping Checks

Before placing unit in operation, leak test the unit and gas
connections.
Check for leaks using an approved chloride-free soap and
water solution, an electronic combustible gas detector, or
other approved testing methods.
NOTE: Never exceed specified pressures for testing.
Higher pressure may damage the gas valve and cause
subsequent overfiring, resulting in heat exchanger
failure.
Disconnect this unit and shutoff valve from the gas supply
piping system before pressure testing the supply piping
system with pressures in excess of 1/2 psig (3.48 kPa).
Isolate this unit from the gas supply piping system by closing
its external manual gas shutoff valve before pressure testing
supply piping system with test pressures equal to or less than
1/2 psig (3.48 kPA).
T
O AVOID THE POSSIBILITY OF EXPLOSION OR FIRE
OR OPEN FLAME TO TEST FOR LEAKS
I
F THE GAS FURNACE IS INSTALLED IN A BASEMENT
,
AREA OR CONFINED SPACE
IT IS STRONGLY RECOMMENDED TO
CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING
DEVICE IN CASE OF A GAS LEAK
S
INCE PROPANE GAS IS HEAVIER THAN AIR
SETTLE IN ANY LOW AREAS OR CONFINED SPACES
P
ROPANE GAS ODORANT MAY FADE
EXCEPT WITH A WARNING DEVICE

Propane Gas Tanks and Piping

A gas detecting warning system is the only reliable way
to detect a propane gas leak. Rust can reduce the level
of odorant in propane gas. Do not rely on your sense
of smell. Contact a local propane gas supplier about
installing a gas detecting warning system. If the presence
of gas is suspected, follow the instructions listed in the
Safety Considerations section of this manual.
All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters,
NBFU Manual 58.
CANADA: National Standard of Canada, Natural Gas and
Propane Installation Code (NSCNGPIC) CSA B149.1-15.
WARNING
,
NEVER USE A MATCH
.
WARNING
,
AN EXCAVATED
.
,
ANY LEAKING GAS CAN
.
,
MAKING THE GAS UNDETECTABLE
.
First Stage
Regulator
200 PSIG
Maximum
Propane Gas Installation (Typ.)
For satisfactory operation, propane gas pressure must be
10" WC at the furnace manifold with all gas appli ances in
operation. Maintaining proper gas pressure depends on
three main factors:
1. Vaporization rate, depending on temperature of the
liquid, and "wetted surface" area of the con tainer or
containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and
between second stage regulator and the appliance.
Pipe size will depend on length of pipe run and total
load of all appliances.
Complete information regarding tank sizing for vaporiza-
tion, recommended regulator settings, and pipe sizing is
available from most regulator manufacturers and propane
gas suppliers.
Since propane gas will quickly dissolve white lead and
most standard com mercial compounds, special pipe dope
must be used. Always use a pipe thread sealant approved
for all gases.
Refer to the illustration for typical propane gas
installations and piping.
N
EVER ALLOW THE PRODUCTS OF COMBUSTION
,
MONOXIDE
TO ENTER THE RETURN DUCT WORK OR CIRCULATION AIR
.
SUPPLY
CIRCULATING AIR & FILTERS

Duct work - Air Flow

Duct systems and register sizes must be properly
designed for the CFM and external static pressure rat ing
of the furnace. Design the ductwork in accor dance with the
recommended methods of "Air Conditioning Contractors
of America" Manual D.
31
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
Figure 41
WARNING
,
INCLUDING CARBON

Advertisement

Table of Contents
loading

This manual is also suitable for:

C9s96 seriesM9s92 series

Table of Contents