Circulating Air & Filters; Duct Work - Air Flow; Checking Duct Static - Amana xMVM97 series Installation Instructions Manual

Modulating gas furnace
Table of Contents

Advertisement

First Stage
Regulator
200 PSIG
Maximum
Propane Gas Installation (Typ.)
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing Size, O.D. Type L
Tubing
Length
Feet
3/8"
1/2"
10
730
1,700
3,200
20
500
1,100
30
400
920
2,000
40
370
850
1,700
50
330
770
1,500
60
300
700
1,300
80
260
610
1,200
100
220
540
1,000
125
200
490
150
190
430
175
170
400
200
160
380
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Propane Gas Piping Chart I
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum Propane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length
Feet
3/8"
1/2"
5/8"
10
39
92
199
20
26
62
131
30
21
50
107
40
19
41
90
50
18
37
79
60
16
35
72
80
13
29
62
100
11
26
55
125
10
24
48
150
9
21
43
200
8
19
39
250
8
17
36
*Data in accordance with NFPA pamphlet No. 54
Propane Gas Piping Chart II
32
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
Figure 39
Nominal Pipe Size
Schedule 40
5/8"
3/4"
7/8"
1/2"
5,300
8,300
3,200
220
3,700
5,800
2,200
2,900
4,700
1,800
2,700
4,100
1,600
2,400
3,700
1,500
2,200
3,300
1,300
1,900
2,900
1,200
1,700
2,600
1,000
900
1,400
2,300
900
830
1,300
2,100
830
780
1,200
1,900
770
730
1,100
1,800
720
Nominal Pipe Size
Schedule 40
3/4"
7/8"
1/2"
3/4"
1"
1-1/4" 1-1/2"
329
501
275
567
1,071 2,205
216
346
189
393
732
1,496
181
277
152
315
590
1,212
145
233
129
267
504
1,039
131
198
114
237
448
913
1,211
187
103
217
409
834
104
155
89
185
346
724
90
138
78
162
307
630
81
122
69
146
275
567
72
109
63
132
252
511
66
100
54
112
209
439
60
93
48
100
185
390
C
IRCULATING
D
- A
UCT WORK
N
EVER ALLOW THE PRODUCTS OF COMBUSTION
,
MONOXIDE
TO ENTER THE RETURN DUCT WORK OR CIRCULATION AIR
.
SUPPLY
Duct systems and register sizes must be properly designed for
the CFM and external static pressure rating of the furnace. De-
sign the ductwork in accordance with the recommended meth-
ods of "Air Conditioning Contractors of America" Manual D.
Install the duct system in accordance with Standards of the Na-
tional Board of Fire Underwriters for the Installation of Air Condi-
tioning, Warm Air Heating and Ventilating Systems. Pamphlets
No. 90A and 90B.
A closed return duct system must be used, with the return duct
3/4"
connected to the furnace. NOTE: Ductwork must never be at-
7,500
tached to the back of the furnace. For upflow installations re-
4,200
4,000
quiring 1800 CFM or more, use either two side returns or bottom
3,700
return or a combination of side and bottom. Flexible joints may
3,400
3,100
be used for supply and return connections to reduce noise trans-
2,600
mission. To prevent the blower from interfering with combustion
2,300
air or draft when a central return is used, a connecting duct must
2,100
1,900
be installed between the unit and the utility room wall. Never
1,700
use a room, closet, or alcove as a return air chamber.
1,500
C
D
HECKING
UCT
Refer to your furnace rating plate for the maximum ESP (ex-
ternal duct static) rating.
Total external static refers to everything external to the fur-
nace cabinet. Cooling coils, filters, ducts, grilles, registers
must all be considered when reading your total external static
pressure. The supply duct pressure must be read between
the furnace and the cooling coil. This reading is usually taken
3,307
2,299
by removing the "A" shaped block off plate from the end on
1,858
the coil; drilling a test hole in it and reinstalling the block off
1,559
1,417
plate. Take a duct static reading at the test hole. Tape up
1,275
the test hole after your test is complete. The negative pres-
1,066
sure must be read between the filter and the furnace blower.
976
866
787
Excessive external static pressure will result in insufficient
665
air which can cause excessive temperature rise. This can
590
cause limit switch tripping and heat exchanger failure.
To determine total external duct static pressure, proceed as
follows;
1. With clean filters in the furnace, use a draft gauge (in-
clined manometer) to measure the static pressure of the
return duct at the inlet of the furnace. (Negative Pres-
sure)
2. Measure the static pressure of the supply duct. (Positive
Pressure)
A
& F
IR
ILTERS
F
IR
LOW
WARNING
,
INCLUDING CARBON
S
TATIC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xcvm97 series*mvm97 series*cvm97 series

Table of Contents