Power Up

Connecting Ground Conductors

To attach the ground wires:
1. Remove the ground screw on the rear of the chassis adjacent to the ground symbol.
2. Place the ring terminal of the 10 AWG (4 mm
screw.
3. Replace the ground screw on the chassis and securely tighten the screw so the screw
cannot be loosened without the use of a tool.
4. Attach the supplementary ground conductor to an approved ground.

Using a Ground Block

A ground block might be provided for use with multiple Media Gateway installations. Usually, the
customer electrician mounts the ground block.
To attach the supplementary ground conductor (that is already attached to the grounding screw
on the chassis) to a ground block:
1. Cut the supplementary ground conductor to the length needed to terminate the conductor
into one of the terminals of the ground block. Do not coil the supplementary ground
conductor.
2. Attach one end of the remaining 10 AWG (4 mm
ground block and the other end to an approved ground. Cut this ground wire to the length
needed to reach the approved ground. Do not coil this wire.
24 Quick Start for Hardware Installation Avaya G350 Media Gateway
2
) supplementary ground conductor on the
2
) ground wire to one of the terminals in the