8.10 List of Access Point system variables
(alphabetical order)
AP_ALTER_ADDR
Alternative address of the Access Point (used if
dipswitch=0) default=1. Used to set an alternative
address to the on set by dipswitch (make sure to
avoid network confl icts); The new address must be
set for parameter AP_ALTER_ADDR (HR_10);
AP_CONN
Indicates whether the Access Point is managing the
wireless network (1 = yes);
AP_OPEN
Indicates that the network is open and new devices
can be bound (1 = yes);
AP_RESET_CNT
Wireless network verifi cation parameters for internal
use;
AP_RESET_TYPE
Wireless network verifi cation parameters for internal
use;
AP_TX_RADIO_LEV
Indicates the wireless transmission and reception le-
vels for the Access Point in dBm +100. For minimum
reception, the value must be greater than 8, medium
quality reception from 15 to 30, and good quality
values greater than 30;
CMD_PASSW_1....7
Commands used to confi gure the wireless network.
Used by installation and confi guration tools;
CONN_AP
Number of units directly connected to the Access
Point;
CONN_BINDED
Total number of units visible in the network from the
remote wired network Bridge (see Bridge);
CONNECTED_UNIT
Total number of sensors connected to the wireless
network and managed by Access Point;
EN_CMD_PW
Commands used to confi gure the wireless network.
Used by installation and confi guration tools;
FREE_BUFFER
Wireless network verifi cation parameters for internal
use;
FW_VERSION
Access Point FW revision
ID_SER_ADDR
Serial address value, set by dipswitch. Can be used as
the unit identifi er;
MAC_ADDR_0
Unique 32 bit unit identifi er (0 = LSB), used to uni-
quely identify each unit;
MAC_ADDR_1
Unique 32 bit unit identifi er (1 = MSB), used to
uniquely identify each unit;
MACHINE_CODE
Peripheral identifi er for the supervisor (112 for the
Access Point);
MAX_SELEC_ADDR
Maximum address value allowed for devices
behind the Router-Bridge, default=247
MIN_SELEC_ADDR
Minimum address value allowed for devices behind
the Router-Bridge, default=1
NET_CHANNEL
ZigBee Network transmission channel. Uniquely
defi nes the wireless network used by the system for
communication (Access Point, Repeaters, Sensors).
The value is set during the confi guration procedure
or using the commissioning tool;
NET_PANID
ZigBee network transmission identifi er. Uniquely
defi nes the wireless network used by the system for
communication (Access Point, Repeaters, Sensors).
The value is set during the confi guration procedure
or using the commissioning tool;
NET_PANID_EXT_0.....3
Network Extended PanID
Network identifi ers. Guarantee greater security on
the wireless network. Fundamental parameters for
cloning the ZigBee network
OFFLINE_MODE
Access Point response mode for units that are Offl ine.
Parameter HR_03 (Operating mode, default value 21;
HR_03 = 21 Communication with Router-Bridge
disabled (default);
HR_03 = 17 Communication with Router-Bridge
enabled. Filters should be confi gured to set the min
and max addresses of the devices connected via
Router-Bridge (HR_11 and HR_12);
Note: a peripheral is considered Offl ine by the Access
Point after 4 query cycles, i.e. after a time of 4 x
TRANSM_CYCLE..
RES_COUNTER
Wireless network verifi cation parameters for internal
use;
ROUTER_CONN_NEARBY
Number of Routers in the vicinity;
ROUTER_CONNECTED
Total number of routers connected to the network;
ROUTER_GOOD_SIGNAL
Number of Routers in the vicinity with a good wire-
less signal, ≥ 30 dB;
ROUTER_TX_TIME
Transmission time for wireless refresh signal (aggre-
gation)
"Wireless probes" +0300030EN - rel. 1.0 - 16.07.2010
RX_MSG_LEVEL
Indicates the wireless transmission and reception le-
vels for the Access Point in dBm +100. For minimum
reception, the value must be greater than 8, medium
quality reception from 15 to 30, and good quality
values greater than 30;
RX_MSG_LEVEL
Wireless network verifi cation parameters for internal
use;
TIME_STAMP
Clock in hours:minutes for recording the times the
sensors measure and send data. This is updated/
incremented every minute by the Access Point, the
value can be set from the supervisor to align it with
a real clock. Invalid values are rounded off to the ne-
arest (hour: minutes). The value is lost in the event of
power failures, restarting from 00:00. If synchronisa-
tion is required, the supervisor must reset the value;
Note:
the parameters described are divided into 4 groups based on the Modbus
standard:
HR_xx Read/write registers (16-bit word)
IR_xx
Read-only registers (16-bit word)
CS_xx
Read/write bits (1-bit)
IS_xx
Read-only bit (1-bit))
Parameters specifi ed as: "Confi guration" or "Verify NETWORK" are not normally
used in the supervisor application. They can on the other hand be used by
confi guration systems (commissioning tool).
36
Tab. 8.e

Advertisement

Table of Contents
loading

Table of Contents