5.4 Sensor installation notes

1.
Remove the cover.
2.
Fasten the case to the wall with minimum two screws, remembering
that this is a radio device and therefore the necessary details must be
observed.
3.
Select the network address on the dipswitches.
4.
Remove the insulating protection on the battery.
5.
Perform the binding procedure.
6.
Check the quality of the wireless signal; stimulate the sensor by pressing
button T1 or activating magnetic switch SW1 and check the fl ashes on
LED L3:
-
1 fl ash, wireless connection with minimum signal strength;
-
2 fl ashes, wireless connection with medium signal strength;
-
3 fl ashes, wireless connection with excellent signal strength;
7.
Close the sensor again.
8.
Make sure that the transmitter is in an optimum position with reference
to the receiver, once installation is complete, checking the transmitted
signal level in the corresponding supervisor variable.

5.5 Physical dimensions

5.6 Application example

22
127
Fig. 5.d
Fig. 5.e
25
Fig. 5.c
22
83
1
L1
+
1
8
L2
L3
2
Key:
1.
Confi guration button / switch;
2.
Serial address dipswitches;