Light intensity alarm function:
HI_LUX_TRESHOLD
LO_LUX_TRESHOLD
ALARM
The sensor compares the temperature, humidity and light intensity measured
against the parameters that defi ne the alarm limits.
There are no delays in activating the alarm signal; as soon as the acquired
value is higher than the maximum limit or lower than the minimum limit the
corresponding fl ag is activated.
If Temperature > High temperature limit --> high temp. alarm =1
If Temperature ≤ High temperature limit --> high temp. alarm =0
If Temperature < Low temperature limit --> low temp. alarm =1
If Temperature ≥ Low temperature limit --> low temp. alarm =0
If Humidity > Maximum humidity limit --> maximum humidity alarm =1
If Humidity ≤ Maximum humidity limit --> maximum humidity alarm =0
If Humidity < Minimum humidity limit --> minimum humidity alarm =1
If Humidity ≥ Minimum humidity limit --> minimum humidity alarm =0
If Light > Maximum light limit --> maximum light alarm =1
If Light ≤ Maximum light limit --> maximum light alarm =0
If Light < Minimum light limit --> minimum light alarm =1
If Light ≥ Minimum light limit --> minimum light alarm =0
6.2 Technical specifi cations
Power supply
3.6V 2500 mAh lithium battery, "AA" size
Maximum power input
100 mW
Battery life in normal operating
From 3 to 8 years, depending on the transmis-
conditions
sion time set. (CAREL is not responsible for the
specifi ed battery life)
Radio frequency specifi cations
Frequency: selectable from 2405 to 2480 MHz
Power transmitted: 0dBm
Wireless protocol: ZigBee
Operating conditions
-20T70 °C
10 to 90 rH%
0 to 100 (Light intensity)
Storage conditions
-20T70 °C - humidity range: <80% RH non-
cond.
Precision of temperature measu-
Temperature ±1°C 0T50 °C
rement and humidity
Humidity ±5 rH%
Light intensity ±20% (depends on the spec-
trum)
Index of protection against atmo-
IP55
spheric agents
Classifi cation according to protec-
Can be integrated into class I or class II
tion against electric shock
appliances
Environmental pollution
Normal
PTI of insulating materials
250 V
Period of stress across the insula-
Long
ting parts
Category of resistance to heat
category D (box and cover)
and fi re
Immunity against voltage surges category 1
Software class and structure
Class A
Disposal
observe local legislation for the disposal of
electrical material
Product code
WS01F01M00 - Wireless industrial temperatu-
re, humidity and light intensity sensor ver. SI
battery powered
Accessories
WS00BAT000 - Battery, single package
0000000722 Magnet for activating SW1
High luminous event started normal condition
Alarm ON
Alarm ON
Fig. 6.d
Tab. 6.a
Alarm ON
27
"Wireless probes" +0300030EN - rel. 1.0 - 16.07.2010