List Of Parameters And Variables, Ci Pulse Counter - Carel BP SE Sensor User Manual

Carel wireless sensors for monitoring environmental conditions - temperature, humidity, light
Table of Contents

Advertisement

7.4 List of parameters and variables, CI Pulse Counter

Below is the table of supervisor parameters for the CI devices; this also applies to the RC Router-Pulse Counter (only for the special pulse counter function).
Variable Index Name
HR0
CMD_PASSW_1
HR1
TRANSM_CYCLE
HR2
CMD_PASSW_2
HR3
CMD_PASSW_3
HR4
INC_COUNTER
HR5
MIN_RSSI_LEVEL
HR6
CNT_REJOIN
IR0
MACHINE_CODE
IR1
FW_VERSION
IR2
TX_MESSAGE_CNT
IR3
RX_MSG_LEVEL
IR4
BATTERY_LEVEL
IR5
PROBE_TMP_DIFF
IR6
TEMPERATURE_1
IR7
TEMPERATURE_2
IR8
IN_1_COUNTER_LOW
IR9
IN_1_COUNTER_HIG
IR10
IN_2_COUNTER_LOW
IR11
IN_2_COUNTER_HIG
IR12
IN_1_LAST_COUNT
IR13
IN_1_LAST_TIME
IR14
IN_2_LAST_COUNT
IR15
IN_2_LAST_TIME
IR16
MAC_ADDR_0
IR17
MAC_ADDR_1
IR18
ID_SER_ADDR
IR19
LAST_RX_DELAY
IR20
RX_MESSAGE_CNT
IR21
TIME_STAMP
IR22
AP_RX_RADIO_LEV
IR23
NETWORK_ID
IR24
'MIRROR_IS'
CS0
EN_CMD_PW
CS1
EN_NTC_1
CS2
EN_NTC_2
IS0
IN_1_STATUS
IS1
IN_2_STATUS
IS2
PROBE_ERROR_1
IS3
PROBE_ERROR_2
IS4
ALM_GENERAL
IS5
LOW_BATT
Key:
HR = Holding register
IR = Input register
CS = Coil Status
IS = Input Status
Description
'Command Password (1)'
'TX data cycle time'
'Command Password (2)'
'Command Password (3)'
'Incrase counter for input'
'Minimum rssi level counted (internal use)'
'Max counter value before rejoin (internal use)'
'Unit type - machine code' (67=ZED, 68=ZR)
'Firmware version (Major/Minor)'
'Total Number of TX radio messages'
'Radio signal Level'
'Battery Level'
'Temperature diff erence NTC1 probe - NTC2 probe'
'Temperature Value probe 1'
'Temperature Value probe 2'
'Input Counter IN_1 (Low)'
'Input Counter IN_1 (High)'
'Input Counter IN_2 (Low)'
'Input Counter IN_2 (High)'
'Input Counter IN_1 in last sampling period'
'Sampling period IN_1'
'Input Counter IN_2 in last sampling period'
'Sampling period IN_2'
'Unit unique identifi er Mac-Address LSB'
'Unit unique identifi er Mac-Address MSB'
'Carel_ID, Serial_Address, DIP-SW value'
'Time from last AP Rx message'
'Counter - AP Rx messages'
'Time stamp for Temp. readings (100*hour+minute)'
'Radio Lev. for AP Rx messages'
'Network address'
'Mirror Input Status (internal use)'
'Trig. PWD (internal use)'
'Enable Probe NTC_1'
'Enable Probe NTC_2'
'Digital Input State IN_1'
'Digital Input State IN_2'
'Probe 1 Failure Alarm'
'Probe 2 Failure Alarm'
'General Unit Alarm'
'Battery Alarm'
Def.
Min
0
60
0
0
1
0
30
67/68
2051
0
0
-
-
-500
-
-500
-
-500
0
0
0
0
0
0
0
0
-
-
-
16
-
-
-
-
-
-
0
1
1
-
-
-
-
-
-
31
"Wireless probes" +0300030EN - rel. 1.0 - 16.07.2010
Max
UoM
"Type R/W"
0
65535
-
5
3600
sec
0
65535
-
0
65535
-
1
100
-
0
99
-
1
255
-
-
-
-
-
-
-
0
65535
-
0
100
dBm+100
0
3600
mV
1000
0,1°C
1000
0,1°C
1000
0,1°C
0
65535
-
0
65535
-
0
65535
-
0
65535
-
0
65535
-
0
65535
sec
0
65535
-
0
65535
sec
0
65535
-
0
65535
-
127
-
0
65535
-
0
65535
-
0
2359
hh*100+mm
0
100
dBm+100
0
65535
-
0
65535
-
0
1
-
0
1
-
0
1
-
0
1
-
0
1
-
0
1
-
0
1
-
0
1
-
0
1
-
ENG
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R
R
R
R
R
R
Tab. 7.b