Acoustic Indicators; Summary Of Status Indications - GE Kilsen KFP-CF Series Operation Manual

Table of Contents

Advertisement

Item
Control/LED
21
Fire Routing
Fault/Disable/Test
button and LED

Acoustic indicators

The control panel uses the following acoustic indicators to highlight system events.
Indication
The internal buzzer sounds
constantly
The internal buzzer sounds
intermittently

Summary of status indications

This section includes a summary of the control panel status indications.
Standby (normal status)
Standby, or normal status, is indicated as follows:
• The Supply LED is steady.
• If a sounder delay was enabled, the Sounder Delay LED is steady.
• If a fire routing delay was enabled, the Fire Routing Delay LED is steady.
• There are no acoustic indications.
Fire alarm
Fire alarm status is indicated as follows:
• The general Fire Alarm LEDs are flashing if the alarm was activated by a detector
or steady if the alarm was activated by a manual call point.
• The corresponding zone alarm LEDs are flashing if the alarm was activated by a
detector or steady if the alarm was activated by a manual call point.
• If a sounder delay was enabled, the Sounder Delay LED is steady. The Sounder
Start/Stop LED flashes while the delay is active. When the sounders are active
(sounding), the LED is steady.
• If a fire routing delay was enabled, the Fire Routing Delay LED is steady. The Fire
Routing Start LED flashes while the delay is active. When fire routing is active, the
LED is steady.
• The internal buzzer sounds constantly.
Alarms activated by a manual call point always take priority over alarms activated by
a detector. If an alarm is activated by both devices, the Fire Alarm LEDs and zone
alarm LEDs are steady.
Kilsen KFP-CF Series Operation Manual
LED colour
Description
Yellow
Indicates that fire routing is in a fault condition, is
disabled, or is being tested.
A flashing LED indicates a fault. A steady LED
indicates that the function is disabled or is being
tested.
Description
Indicates a fire alarm or a system
fault
Indicates all other faults