Item
Control/LED
10
General Disable
button and LED
11
General Test button
and LED
12
Numeric keypad and
Enter button
13
Reset button
14
Panel Silence button
and LED
15
Sounder Start/Stop
button and LED
16
System Fault LED
17
Out of Service LED
18
Earth Fault LED
19
Supply Fault LED
20
Fire Routing Delay
button and LED
21
Fire Routing Start
button and LED
6
LED colour
Description
Yellow
Disables a zone, sounders, fire routing, or expansion
I/O module (when pressed with the corresponding
button).
A steady general Disable LED and the corresponding
zone, sounders, or fire routing Fault/Disable/Test
LED indicates a disablement.
Yellow
Tests a zone, sounders, or fire routing (when pressed
with the corresponding button).
A steady general Test LED and the corresponding
zone, sounders, or fire routing Fault/Disable/Test
LED indicates a test.
N/A
Used to enter the access level 2 password. The Enter
button is also used to disable expansion I/O modules
(when pressed with the general Disable button).
Yellow
Resets the control panel and clears all current
system events (except expansion I/O module fault
communication).
A steady LED indicates that access level 2 is active
(see "Access levels" on page 10).
Yellow
Silences the internal buzzer and acknowledges all
current events.
A steady LED indicates that all current events were
acknowledged.
Red
Stops (silences) all active sounders. Pressing the
button again restarts them.
A flashing LED indicates that sounders activate
when a configured delay elapses. A steady LED
indicates that the sounders are active (sounding).
Yellow
Indicates a control panel CPU failure.
Yellow
Indicates that the control panel is not operational.
Yellow
Indicates an earth fault.
Yellow
Indicates a fault with the power supply.
A flashing LED indicates a battery or battery fuse
fault. A steady LED indicates a mains or mains fuse
fault.
Yellow
Enables or disables a previously configured fire
routing delay.
A steady LED indicates that a fire routing delay is
configured and enabled.
Red
Cancels a previously configured delay and activates
fire routing.
A flashing LED indicates that fire routing activates
when the configured delay elapses. A steady LED
indicates that fire routing is active.
Kilsen KFP-CF Series Operation Manual