WARNING:
No fire alarm or faults are indicated for disabled zones.
Testing sounders
To test sounders, press the general Test button, and then press the Sounder
Fault/Disable/Test button. Sounders can only be tested when the control panel is in
standby.
The test is indicated as follows:
• The general Test LED is steady.
• The Sounder Fault/Disable/Test LED is steady.
• The sounders emit the audible test signal (three seconds on, five seconds off) for
the duration of the test, without any configured delay.
To end the test, press the general Test button, and then press the Sounder Start/Stop
button again.
If there is a fire alarm the fire panel will exit the test immediately and respond to the
alarm as configured.
Disabling sounders or enabling disabled sounders
To disable sounders, press the general Disable button, and then press the Sounder
Fault/Disable/Test button. Sounders can only be disabled when the control panel is in
standby.
Disabled sounders are indicated as follows:
• The general Disable LED is steady.
• The Sounder Fault/Disable/Test LED is steady.
To enable the sounders, press the general Disable button, and then press the
Sounder Fault/Disable/Test button again.
WARNING:
Disabled sounders do not indicate a fault or operate if there is a fire
alarm.
Testing fire routing
Caution:
Always notify the fire brigade of any planned fire routing tests.
To test fire routing, press the general Test button, and then press the Fire Routing
Start button.
The test is indicated as follows:
• The general Test LED is steady.
• The Fire Routing Fault/Disable/Test LED is steady.
• The Fire Routing Start LED flashes and the test signal (three seconds on/five
seconds off) is activated without any configured delay for the duration of the test.
To end the test, press the general Test button, and then press the Fire Routing Start
button again.