Supply water temperature sensor
Return water temperature sensor
IBC Outdoor Sensor
10KΩ Temperature sensors
supplied with boiler (above)
See table #9 for resistance values
5-2
SL 35-199, SL 45-260 MODULATING GAS BOILERS
5.2
This section details the method for troubleshooting the non-standard electronic
components on the boiler including the electronic differential air pressure sensor
and the temperature sensors.
5.2.1 Temperature Sensors
The resistance of the temperature sensors varies inversely with temperature. To
test, measure the temperature of the sensed environment and compare with the
value derived from the measurement of the resistance (obtained by connecting a
good quality test meter capable of measuring up to 5,000 kΩ (5,000,000Ω) at the
controller end of the sensor lead).
To obtain a resistance reading, remove power to the boiler. For the supply water
and return water temperature sensors, remove the wire leads by disconnecting
their respective Molex connectors. Place multi-meter probes into sensor's female
Molex connector socket. Do not apply voltage to the sensor (damage may result).
TEMPERATURE
°F
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
Table 9: Temperature Sensor resistance values
RESISTANCE
°C
Ω
-18
85,362
-15
72,918
-12
62,465
-9
53,658
-7
42,218
-4
39,913
-1
34,558
2
29,996
4
26,099
7
22,763
10
19,900
13
17,436
16
15,311
18
13,474
21
11,883
24
10,501
27
9,299
29
8,250
32
7,334
35
6,532
INSTALLATION AND OPERATION INSTRUCTIONS
TEMPERATURE
RESISTANCE
°F
°C
100
38
105
41
110
43
115
46
120
49
125
52
130
54
135
57
140
60
145
63
150
66
155
68
160
71
165
74
170
77
175
79
180
82
185
85
190
88
195
91
Ω
5,828
5,210
4,665
4,184
3,760
3,383
3,050
2,754
2,490
2,255
2,045
1,857
1,689
1,538
1,403
1,281
1,172
1,073
983
903