Troubleshooting
9.3 How to Check Simply the Main Part
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Pionts:
Use AC voltmeter to check if the voltage between terminal L and N on the wiring board id within 210VAC~240VAC.
If the reactor (L) is correctly connected? If the connection is loose or fallen? If the reactor (L) is damaged?
Fault diagnosis process:
Measure the AC voltage between
terminal L and N on wiring board
XT(power supply)
Shut down the power and wait 20 minutes; or
use DC voltmeter to measure the voltage on the
two ends of capacitor, until the voltage is lower
than 20V
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Y
Voltage higher than 200V?
N
Voltage within
210VAC~250VAC?
Y
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
If the wiring of
N
reactor L is normal?
Y
Replace the control
panel AP1
End
Fault with the voltage
testing circuit on
control panel AP1
Shut down the power
and repair the power
supply to restore the
N
range
210VAC~250VAC
Connect the reactor L
according to Electrical
Wiring Diagram
correctly
Replace the control
panel AP1
power on and
If the fault is eliminated?
restar t the unit
N
Re-energize and
If the fault is eliminated?
turn on the unit
N
Y
Y