Models:
GWH09RB-K3DNA3G
GWH12RB-K3DNA3G
(Refrigerant:R410A)
GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI

Advertisement

Table of Contents
loading

Summary of Contents for Gree GWH09RB-K3DNA3G

  • Page 1 Change for Life Service Manual Models: GWH09RB-K3DNA3G GWH12RB-K3DNA3G (Refrigerant:R410A) GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI...
  • Page 2: Table Of Contents

    Service Manual Table of Contents Part Ⅰ : Technical Information ...............1 1. Summary ........................1 2. Specifications ......................2 2.1 Specification Sheet ......................2 2.2 Operation Characteristic Curve ..................4 2.3 Capacity Variation Ratio According to Temperature ............4 2.4 Cooling and Heating Data Sheet in Rated Frequency .............5 2.5 Noise Curve ........................5 3.
  • Page 3 Service Manual 9. Maintenance ......................30 9.1 Error Code List .......................30 9.2 Procedure of Troubleshooting ..................37 9.3 Troubleshooting for Normal Malfunction .................52 10. Exploded View and Parts List ..............54 10.1 Indoor Unit ........................54 10.2 Outdoor Unit .........................56 11. Removal Procedure ..................58 11.1 Removal Procedure of Indoor Unit ................58 11.2 Removal Procedure of Outdoor Unit ................65 Appendix:...
  • Page 4: Part Ⅰ : Technical Information

    Service Manual Part Ⅰ : Technical Information 1. Summary Indoor Unit GWH09RB-K3DNA3G/I GWH12RB-K3DNA3G/I Outdoor Unit GWH09MB-K3DNE3G/O GWH12MB-K3DNE3G/O Remote Controller YAA1FB Technical Information...
  • Page 5: Specifications

    Service Manual 2. Specifications 2.1 Specification Sheet Model GWH09RB-K3DNA3G GWH12RB-K3DNA3G Product Code CB302003100 CB302003200 Rated Voltage 220-240 220-240 Power Rated Frequency Supply Phases Power Supply Mode Outdoor Outdoor Cooling Capacity 2600(600~3200) 3500(600~3900) Heating Capacity 3000(800~3600) 4000(880~4400) Cooling Power Input 870(185~1300)
  • Page 6 Service Manual Model of Outdoor Unit GWH09MB-K3DNE3G/O GWH12MB-K3DNE3G/O Outdoor Unit Product Code CB404W03600 CB404W03500 ZHUHAI LANDA ZHUHAI LANDA Compressor Manufacturer/Trademark COMPRESSOR CO., LTD. COMPRESSOR CO., LTD. Compressor Model QXA-A091zE190A QXA-A091zE190A Compressor Oil RB68EP RB68EP Compressor Type Rotary Rotary L.R.A. 16.5 16.5 Compressor RLA Compressor Power Input...
  • Page 7: Operation Characteristic Curve

    Service Manual 2.2 Operation Characteristic Curve Cooling Heating Condition Condition Indoor:DB 20 °C Indoor:DB 27 WB19 °C °C Indoor air flow:Turbo Indoor air flow: Turbo Pipe length:5m Pipe length:5m Voltage:230V Voltage:230V Compressor Speed(rps) Compressor Speed(rps) 2.3 Capacity Variation Ratio According to Temperature Cooling Heating Cooling...
  • Page 8: Cooling And Heating Data Sheet In Rated Frequency

    Service Manual 2.4 Cooling and Heating Data Sheet in Rated Frequency Cooling: Rated cooling Pressure of gas pipe Inlet and outlet pipe Compressor condition( connecting indoor and temperature of heat Fan speed of Fan speed of Model frequency (DB/WB) outdoor unit exchanger indoor unit outdoor unit...
  • Page 9: Outline Dimension Diagram

    Service Manual 3. Outline Dimension Diagram 3.1 Indoor Unit Φ55 Φ55 Unit:mm 3.2 Outoor Unit Unit:mm Technical Information...
  • Page 10: Refrigerant System Diagram

    Service Manual 4. Refrigerant System Diagram Indoor unit Outdoor unit Gas pipe side Valve 4-Way valve Di s charge Heat Suction Accumlator exchanger Compressor (evaporator) Heat exchanger Liquid pipe (condenser) side Valve Strainer Capillary Electron Strainer expansion valve COOLING HEATING Connection pipe specification: Liquid pipe:1/4"...
  • Page 11: Electrical Part

    Service Manual 5. Electrical Part 5.1 Wiring Diagram ●Instruction Symbol Symbol Color Symbol Symbol Color Symbol Name White Green Jumper cap Yellow Brown COMP Compressor Blue Grounding wire YEGN Yellow/Green Black Violet Orange Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model. ●...
  • Page 12 Service Manual ● Outdoor Unit The electrical NOTE: heaters are Motor ground only optional. applies to the iron shell motor. These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit. Technical Information...
  • Page 13: Pcb Printed Diagram

    Service Manual 5.2 PCB Printed Diagram Indoor Unit ● Top view Name Interface of live wire Interface of live wire for outdoor control Fuse Interface of neutral wire Interface of neutral wire for health function Control interface of PG motor Interface of live wire for health function Interface of indoor...
  • Page 14 Service Manual Outdoor Unit ● Top view Name 1 Inductance pin2 2 Inductance pin1 3 Four-wayvalve 4 Compressor electric heater 5 Chassis electric heater 6 Fan neilsbed 7 Electric expansion valve 8 Temp. sensor 9 Main chip 10 EEPROM ● Bottom view Technical Information...
  • Page 15: Function And Control

    Service Manual 6. Function and Control 6.1 Remote Controller Introduction Buttons on Remote Controller ON/OFF button ON/OFF button - button - button + button + button MODE button MODE button H O U R ONOFF FAN button H O U R ONOFF FAN button SWING button...
  • Page 16 Service Manual Press this button to turn on the unit. Press this button again to turn off the unit. 2. - Button Press this button to decrease set temperature. Holding it down above 2 seconds rapidly decreases set temperature. In AUTO mode, set temperature is not adjustable.
  • Page 17 Service Manual ● When selecting " " by remote controller or no display, temperature indicator on indoor unit displays set temperature. ● When selecting " " by remote controller, temperature indicator on indoor unit displays indoor ambient temperature. ● When selecting " "...
  • Page 18: Replacement Of Batteries In Remote Controller

    Service Manual Replacement of Batteries in Remote Controller 1.Press the back side of remote controller marked with“ ”as shown in the fig, and then push out the cover of battery box along the arrow direction. 2. Replace two 7# (AAA 1.5V) dry batteries, and make sure the position of “+” polar and “-“ polar are correct. 3.
  • Page 19: Brief Description Of Modes And Functions

    Service Manual 6.2 Brief Description of Modes and Functions 1. Temperature Parameters ◆ Indoor preset temperature (T preset ◆ Indoor ambient temperature (T amb. 2. Basic Functions Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory function is available, for the first energization, if the compressor is at stop before de-energization, the compressor will be started without a 3-minute lag;...
  • Page 20 Service Manual the compressor stops. ◆ When compressor is running (not including each malfunction and protection): a.When outdoor ambient temperature≥20°C and indoor fan speed is low or medium, the fan speed will turn to high; if indoor fan speed is high or super high, it will keep the same. b.When outdoor ambient temperature≤18°C, the fan speed will resume set fan speed.
  • Page 21 Service Manual c.For heating and cooling unit, when (19°C+T ) < T < 26°C (for cooling only unit, 22°C < T < 26°C), it will supplementary indoor ambient indoor ambient keep the original running mode. If the unit is energized for the first time, it will run in fan mode. ②...
  • Page 22 Service Manual (5) SLEEP State Control a. When the air conditioner is under the mode of COOL, and the SLEEP mode has been set well, after the SLEEP state keeps about 1 hour, the pre-setting T will raise 1°C, and it will raise 1°C again after 2 hours, so it raise 2°C in 2 hours, then it will run on at the setting temperature and wind speed.
  • Page 23 Service Manual F3: Outdoor ambient sensor start and short circuit (continuously measured failure in 30s) F4: Outdoor condenser sensor start and short circuit (continuously measured failure in 30s, and don’t measure within 10 minutes after defrosted) F5: Outdoor exhausting sensor start and short circuit (continuously measured failure in 30s after the compressor operated 3 minutes) H3: Overload protection of compressor H5: Module protection PH: High-voltage protection...
  • Page 24: Part Ⅱ : Installation And Maintenance

    Service Manual Part Ⅱ : Installation and Maintenance 7. Notes for Installation and Maintenance Safety Precautions: 10. If the power cord or connection wire is not long enough, please get the specialized power cord or connection wire Important! from the manufacture or distributor. Prohibit prolong the wire by yourself.
  • Page 25 Service Manual Main Tools for Installation and Maintenance 1. Level meter, measuring tape 2. Screw driver 3. Impact drill, drill head, electric drill 4. Electroprobe 5. Universal meter 6. Torque wrench, open-end wrench, inner hexagon spanner 7. Electronic leakage detector 8.
  • Page 26: Installation

    Service Manual 8. Installation 8.1 Installation Dimension Diagram Space to the wall At least 15cm At least 15cm Space to the wall Drainage pipe Installation and Maintenance...
  • Page 27: Installation Procedures

    Service Manual Installation procedures Start installation Preparation before installation Read the requirements select installation Prepare tools for electric connection location Select indoor unit Select outdoor unit installation location installation location Install the support of outdoor unit Install wall-mounting (select it according to the actual situation) frame, drill wall holes Connect pipes of indoor Fix outdoor unit...
  • Page 28: Installation Parts-Checking

    Service Manual 8.2 Installation Parts-checking 8.4 Electric Connection Requirement Name Name 1. Safety Precaution Indoor unit Sealing gum (1) Must follow the electric safety regulations when installing Outdoor unit Wrapping tape the unit. Support of outdoor (2) According to the local safety regulations, use qualified Connection pipe unit power supply circuit and air switch.
  • Page 29 Service Manual in the holes. 5. Connect the Pipe of Indoor Unit (3) Fix the wall-mounting frame on the wall with tapping screws (1) Aim the pipe joint at the corresponding bellmouth.(As show (ST4.2X25TA) and then check if the frame is firmly installed by in Fig.5) pulling the frame.
  • Page 30 Service Manual 7. Connect Wire of Indoor Unit 8. Bind up Pipe (1) Open the panel, remove the screw on the wiring cover and (1) Bind up the connection pipe, power cord and drain hose then take down the cover.(As show in Fig.11) with the band.(As show in Fig.14) (2) Reserve a certain length of drain hose and power cord Screw...
  • Page 31: Installation Of Outdoor Unit

    Service Manual Refer to the following table for wrench moment of force: 8.6 Installation of Outdoor Unit Tightening torque(N . m) Hex nut diameter(mm) 1. Fix the Support of Outdoor Unit(Select it according to Φ6 15~20 the actual installation situation) Φ9.52 30~40 Φ12...
  • Page 32: Vacuum Pumping And Leak Detection

    Service Manual (3) The water outlet can't be placed in water in order to drain 8.8 Check after Installation and Test smoothly.(As show in Fig.27) Operation 1. Check after Installation Check according to the following requirement after finishing installation. The drain hose can't be fluctuant Items to be checked Possible malfunction Has the unit been...
  • Page 33: Maintenance

    Service Manual 9. Maintenance 9.1 Error Code List Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s)
  • Page 34 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 35 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 36 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 37 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 38 Service Manual Display Method of Outdoor Display Method of Indoor Unit Unit Indicator has 3 kinds of Indicator Display (during display status and during Malfunction blinking, ON 0.5s and OFF Dual-8 A/C status Possible Causes blinking, ON 0.5s and OFF Name 0.5s) Code...
  • Page 39 Service Manual Display Method of Indoor Unit Display Method of Outdoor Unit Indicator Display (during Indicator has 3 kinds of display blinking, ON 0.5s and OFF status and during blinking, ON Dual-8 Malfunction A/C status Possible Causes 0.5s) 0.5s and OFF 0.5s Code Name Operation...
  • Page 40: Procedure Of Troubleshooting

    Service Manual 9.2 Procedure of Troubleshooting Indoor Unit 1. Malfunction of Temperature Sensor F1, F2 Main detection points: ● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted? ● Is there short circuit due to trip-over of the parts? ●...
  • Page 41 Service Manual 2. Malfunction of Blocked Protection of IDU Fan Motor H6 Main detection points: ● SmoothlyIs the control terminal of PG motor connected tightly? ● SmoothlyIs the feedback interface of PG motor connected tightly? ● The fan motor can't operate? ●...
  • Page 42 Service Manual 3. Malfunction of Protection of Jumper Cap C5 Main detection points: ● Is there jumper cap on the mainboard? ● Is the jumper cap inserted correctly and tightly? ● The jumper is broken? ● The motor is broken? ●...
  • Page 43 Service Manual 4. Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8 Main detection points: ● Instant energization afte de-energization while the capacitordischarges slowly? ● The zero-cross detectioncircuit of the mainboard is defined abnormal? Malfunction diagnosis process: Start Turn power off for 1minute,the turn...
  • Page 44 Service Manual Outdoor Unit 1. Capacity charging malfunction (outdoor unit malfunction) (AP1 below means control board of outdoor unit) Main detection points: ● Detect if the voltage of L and N terminal of XT wiring board is between 210VAC-240VAC by alternating voltage meter; ●...
  • Page 45 Service Manual 2. IPM protection(H5), desynchronizing malfunction(H7), overcurrent of compressor phase current (P5) (AP1 below means control board of outdoor unit) Main detection points: ● Is voltage input within the normal range ● If the control board AP1 is well connected with compressor COMP? If they are loosened? If the connection sequence is correct? ●...
  • Page 46 Service Manual 3. High temperature and overload protection (E8)(AP1 below means control board of outdoor unit) E8 Main detection points: ● If the outdoor ambient temperature is in normal range; ● If the indoor and outdoor fan are running normally; ●...
  • Page 47 Service Manual 4. Start-up failure (LC) (AP1 below means control board of outdoor unit) Main detection points: ● If the compressor wiring is correct? ● If the stop time of compressor is sufficient? ● If the compressor is damaged? ● If the refrigerant charging amount is too much? Malfunction diagnosis process: Turn on the unit The stop time is not sufficient and...
  • Page 48 Service Manual 5. Overload and high discharge temperature malfunction H3/E4 Main detection points: ● If the electronic expansion valve is connected well? Is the electronic expansion valve damaged? ● If the refrigerant is leaked? ● The compressor overload protection terminal is not connected well with the mainboard? ●...
  • Page 49 Service Manual H3 or E4 is displayed 30min after power off the unit If the overload protector SAT is well connected? Under ambient temperature, test the resistance of overload protector with ohmmeter; resistance value should be<1000ohm Connect wire If the wiring terminal FA of electronic according to wiring expansion valve is well connected? diagram...
  • Page 50 Service Manual 6. PFC (correction for power factor) malfunction (outdoor unit malfunction) Main detection points: ● Check if power plug is connected well with the socket ● Check if the reactor of outdoor unit is damaged? Malfunction diagnosis process: start If power plug is connected Is the malfunction Connect the plug correctly...
  • Page 51 Service Manual 7. Communication malfunction (E6) Main detection points: ● Check if the connection wire and the built-in wiring of indoor and outdoor unit are connected well and without damage; ● If the communication circuit of indoor mainboard is damaged? If the communication circuit of outdoor mainboard (AP1) is damaged? Malfunction diagnosis process: If the unit operates normally...
  • Page 52 Service Manual 8. Malfunction of Overcurrent Protection E5 Main detection points: ● Is the supply voltage unstable with big fluctuation? ● Is the supply voltage too low with overload? ● Hardware trouble? Malfunction diagnosis process: Start Normal fluctuation should be within 10 % Is malfunction Is the supply voltage unstable of the rated voltage on the nameplate...
  • Page 53 Service Manual 9. Flow chart for outdoor communitcation circuit detecting: (1) Test the voltage between N point of wiring board and communication cable with universal meter. The voltage shall be variable. Otherwise, it might be malfunction of mainboard of indoor unit, or malfunction of mainboard of outdoor unit, or wrong wire connection of indoor and outdoor unit.
  • Page 54 Service Manual Start Measure voltage at the Test 10 position as shown in the diagram with a voltmeter Value jumping Measure voltage at the Test 15 position as shown in the diagram with a voltmeter Value jumping Fault with outdoor unit Measure voltage at the Test 11 position as shown in the diagram...
  • Page 55: Troubleshooting For Normal Malfunction

    Service Manual 9.3 Troubleshooting for Normal Malfunction 1. Air Conditioner Can't be Started Up Possible Causes Discriminating Method (Air conditioner Status) Troubleshooting Confirm whether it's due to power failure. If yes, No power supply, or poor After energization, operation indicator isn’t bright wait for power recovery.
  • Page 56 Service Manual 4. Air Conditioner is Leaking Possible causes Discriminating method (air conditioner status) Troubleshooting Eliminate the foreign objects inside the drain Drain pipe is blocked Water leaking from indoor unit pipe Drain pipe is broken Water leaking from drain pipe Replace drain pipe Water leaking from the pipe connection place of Wrapping is not tight...
  • Page 57: Exploded View And Parts List

    Service Manual 10. Exploded View and Parts List 10.1 Indoor Unit Installation and Maintenance...
  • Page 58 Service Manual Part Code Description GWH09RB-K3DNA3G/I GWH12RB-K3DNA3G/I Product Code CB302N03100 CB302N03200 Front Panel Assy 20012858 20012858 Display Board 30565121 30565121 Filter Sub-Assy 1112220403 1112220403 Screw Cover 24252016 24252016 Electric Box Cover2 20122075 20122075 Front Case 20012665 20012665 Axile Bush 10542036...
  • Page 59: Outdoor Unit

    Service Manual 10.2 Outdoor Unit Installation and Maintenance...
  • Page 60 Service Manual Part Code Description GWH09MB-K3DNE3G/O GWH12MB-K3DNE3G/O Product Code CB404W03600 CB404W03500 Front Grill 22413008 22413008 Front Panel Assy 0153304810 0153304810 Axial Flow Fan 10333004 10333004 Chassis Sub-assy 0280330401P 02803304P Clapboard Sub-Assy 0123338502 0123338502 Drainage Connecter 06123401 06123401 Compressor Gasket 76710302 76710302 4-Way Valve Assy 03073151...
  • Page 61: Removal Procedure

    Service Manual 11. Removal Procedure Warning: Be sure to wait for a minimum of 20 minutes after turning off all power supplies and discharge the refrigerant completely before removal. 11.1 Removal Procedure of Indoor Unit Steps Procedure 1. Before disassembly Before disassembly Remove the filter Open the front panel.
  • Page 62 Service Manual Steps Procedure Remove the horizontal louver Remove the axile bush on the horizontal louver. axile bush Pull the horizontal louver outward to remove it. horizontal louver 4. Remove the panel panel Loosen the screws fixing the indicator. Remove the indicator. display Along the groove fixing front panel, slide the rotor shaft outward to remove the...
  • Page 63 Service Manual Steps Procedure Remove the electric box cover Loosen the screw of the electric box cover. electric box cover Remove the electric box cover. Remove the front case Open the screw cap on the front case. Remove the screws fixing the front case. clasps Loosen the clasps of the front case.
  • Page 64 Service Manual Steps Procedure Remove the front case. front case 7. Remove the vertical louver Loosen the 10 clasps connecting the vertical louver and bottom case subassembly. clasps Remove the vertical louver. vertical louver 8. Remove the electric box subassembly temperature sensor Disconnect the indoor tube temperature sensor.
  • Page 65 Service Manual Steps Procedure ground wire screw Remove the screws at the joint of the ground wire and evaporator. Loosen the clasp at the joint of the electric box cover and the electric box. electric box Disconnect the wiring terminal of the wiring terminal motor and step motor on the electric of motor...
  • Page 66 Service Manual Steps Procedure 9. Remove press plate of connecting pipe Pipe Clamp Auxiliary piping Remove the screws of the press plate of connecting pipe. Remove press plate of connecting pipe. 10. Remove the evaporator Remove the screws at the joint of the evaporator and bottom case.
  • Page 67 Service Manual Steps Procedure Auxiliary piping Adjust the pipe slightly to separate the connecting pipe and the evaporator. Remove the evaporator. evaporator 11. Remove motor and cross flow fan step motor Remove the screw of the step motor and remove the step motor. press plate Remove the screw of the motor press plate.
  • Page 68: Removal Procedure Of Outdoor Unit

    Service Manual 11.2 Removal Procedure of Outdoor Unit Steps Procedure 1.Remove big handle Before disassamble Remove 1 connection screw fixing big Big handle handleand then removethe big handle. 2. Remove top cover Top cover Remove 3 connection screws among top cover plate, front panel and right sideplate.
  • Page 69 Service Manual 3.Remove grille and front panel Remove connection screws between the front grille and the front panel. Then remove the front grille. Remove connection screws connecting the front panel with the chassis and the motor support, and then remove the front panel. Grille Panel 4.Remove axial flow blade...
  • Page 70 Service Manual 6.Remove electric box assy Electric box assy Remove the 2 screws fixing the cover of elec- tric box. Lift to remove the cover. Loosen the wire and disconnect the terminal. Lift to re- move the electric box assy. 7.Remove 4-way valve assy Unscrew the fastening nut of the 4-way Valve 4-way Valve Assy...
  • Page 71 Service Manual 9.Remove motor and motor support Motor support Remove the 4 tapping screws fixing the motor. Pull out the lead-out wire and remove the Motor motor. Remove the 2 tapping screws fixing the motor support. Lift motor support to re- move it.
  • Page 72 Service Manual 11.Remove Compressor Remove the 2 screws fixing the gas valve. Unsolder the welding spot connecting gas valve and air return pipe and remove the gas valve. (Note: it is necessary to warp the gas valve when unsoldering the welding spot.) Remove the 2 Liquid valve screws fixing liquid valve.
  • Page 73: Appendix

    Service Manual Appendix: Appendix 1: Reference Sheet of Celsius and Fahrenheit Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32 Set temperature Fahrenheit Fahrenheit Fahrenheit display Fahrenheit display Fahrenheit display Fahrenheit Celsius( Celsius( Celsius( temperature temperature temperature 60.8 69/70 69.8 78/79 78.8 62/63...
  • Page 74: Appendix 3: Pipe Expanding Method

    Service Manual Appendix 3: Pipe Expanding Method Pipe Note: Pipe cutter Improper pipe expanding is the main cause of refrigerant leakage.Please expand the pipe according to the following steps: Leaning Uneven Burr A:Cut the pip ● Confirm the pipe length according to the distance of indoor unit and outdoor unit. ●...
  • Page 75: Appendix 4: List Of Resistance For Temperature Sensor

    Service Manual Appendix 4: List of Resistance for Temperature Sensor Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor(15K) Temp( C) Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( Resistance(kΩ) 138.1 18.75 3.848 1.071 128.6 17.93 3.711 1.039 121.6 17.14 3.579 1.009 16.39...
  • Page 76 Service Manual Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K) Temp( C) Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( Resistance(kΩ) 181.4 25.01 5.13 1.427 171.4 23.9 4.948 1.386 162.1 22.85 4.773 1.346 153.3 21.85 4.605 1.307 20.9 4.443 1.269 137.2...
  • Page 77 Service Manual Resistance Table of Discharge Temperature Sensor for Outdoor(50K) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) Temp( C) Resistance(kΩ) Temp( Resistance(kΩ) 853.5 18.34 4.75 799.8 93.42 17.65 4.61 89.07 16.99 4.47 703.8 84.95 16.36 4.33 660.8 81.05 15.75 4.20 620.8 77.35 15.17 4.08 580.6...
  • Page 78 GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 Email: gree@gree.com.cn Http://www.gree.com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add: Unit 2612,26/F.,Miramar Tower 132 Nathan Road,TST,Kowloon,HK Tel: (852) 31658898 Fax: (852) 31651029...