MAIN BURNER LIGHTS
YES
SPARK STOPS WHEN
BURNER LIGHTS
YES
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS
YES
CALL FOR HEAT ENDS:
SYSTEM SHUTS OFF
YES
TROUBLESHOOTING ENDS
CHECK FOR 25 VAC ACROSS VALVE AND
VALVE TERMINALS IN IGNITER AND CAP, IF
NO
NO VOLTAGE, REPLACE IGNITION CON-
TROL
SPARK IGNITER MAY BE OUT OF POSITION
CHECK ELECTRICAL CONNECTION BE
TWEEN IGNITION CONTROL AND GAS CON
TROL, IF OKAY, REPLACE GAS CONTROL
NOTE: IF IGNITION CONTROL GOES INTO
LOCKOUT, RESET SYSTEM
NO
CHECK CONTINUITY OF SENSOR CABLE
AND GROUND WIRE
CHECK THAT BURNER FLAME COVERS
ALL ELECTRODES
IF CHECKS ARE OKAY, REPLACE IGNITION
CONTROL
NO
CHECK CONTINUITY OF SENSOR CABLE
AND GROUND WIRE
NOTE: IF GROUND IS POOR OR ERRATIC,
SHUTDOWNS MAY OCCUR OCCASIONALLY,
EVEN THOUGH OPERATION IS NORMAL AT
THE TIME OF CHECKOUT IF CHECKS ARE
OKAY, REPACE IGNITION CONTROL
CHECK FOR PROPER TEMPERATURE
NO
CONTROLLER OPERATIONS
REMOVE VALVE LEAD AT IGNITION
CONTROL, IF VALVE CLOSES, RECHECK
TEMPERATURE CONTROLLER AND WIR
ING, IF NOT, REPLACE GAS CONTROL.OR
Page 21
NOTE: IF IGNITION CONTROL GOES INTO
LOCKOUT, RESET SYSTEM
SP-MSTR-AC-11A
STR Manual
RD: NOV, 2003
RL: 11
KH