Mitsubishi Heavy Industries FDC280KXZE1 Service Manual page 60

Kxz standard and corrosion protection treatment series vrf inverter multi-system air-conditioners
Table of Contents

Advertisement

Code
Write-in contents
No.
43
Under-dome super heat CM1
44
Under-dome super heat CM2
45
Target FK
46
Inverter CM1 operation frequency
Inverter CM2 operation frequency
47
48
FMo1 rotation command
49
FMo2 rotation command
50
EEVH1 opening angle
51
EEVH2 opening angle
52
EEVSC opening angle
53
EEVD opening angle
Target cooling low pressure of compressor
54
55
Target heating high pressure of compressor
56
Target differential temperature of heating CSST
57
Spare
58
Target super heat of outdoor unit EEVSC
59
Spare
60
Spare
61
Spare
62
Output of relay
63
Output of relay
64
Output of relay
65
Compressor 1 cumulative operating time (estimate)
Data write-in
Number of
Write-in unit
range
bytes
-32768~
0.01ºC
2
-32767
-32768~
0.01ºC
2
-32767
0~65535
1Hz
2
0~255
1Hz
1
0~255
1Hz
1
0~2550
10 min
1
-1
0~2550
10 min
1
-1
0~65535
1pulse
2
0~65535
1pulse
2
0~65535
1pulse
2
0~65535
1pulse
2
1
0.00~2.00
0.01MPa
0.00~4.15
0.01MPa
2
0~127
1ºC
1
1
0~25.5
0.1ºC
1
1
1
1
1
1
1
0~65535
h
2
28
58
-
-
-
-
'14 • KX-SM-202
Record data
Contents
(Spare)
Real range is 5~30 deg
Bit0
52C1
0: OFF, 1: ON
Bit1
52C2
0: OFF, 1: ON
Bit2
CH1
0: OFF, 1: ON
Bit3
CH2
0: OFF, 1: ON
Bit4
20S
0: OFF, 1: ON
Bit5
Spare(20S)
0: OFF, 1: ON
Bit6
FMC1,2
0: OFF, 1: ON
Bit7
Spare(FMC3)
0: OFF, 1: ON
Bit0
SV1
0: OFF, 1: ON
Bit1
SV2(20UF)
0: OFF, 1: ON
Bit2
Spare(SV4)
0: OFF, 1: ON
Bit3
SV6
0: OFF, 1: ON
Bit4
SV7
0: OFF, 1: ON
Bit5
Spare(SV8)
0: OFF, 1: ON
Bit6
Spare(SV10)
0: OFF, 1: ON
Bit7
SV11
0: OFF, 1: ON
Bit0
Spare(SV12)
0: OFF, 1: ON
Bit1
Spare(SV13)
0: OFF, 1: ON
Bit2
Spare
0: OFF, 1: ON
Bit3
Spare
0: OFF, 1: ON
Bit4
Spare
0: OFF, 1: ON
Bit5
CNZ1
0: OFF, 1: ON
Bit6
CnH
0: OFF, 1: ON
Bit7
CnY
0: OFF, 1: ON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents