Mitsubishi Heavy Industries FDC280KXZE1 Service Manual page 53

Kxz standard and corrosion protection treatment series vrf inverter multi-system air-conditioners
Table of Contents

Advertisement

Code
Contents of display
No.
C59
FMo1 operating revolution command
C60
FMo2 operating revolution command
C61
Demand ratio
C65
Outdoor operating mode pattern
C66
Control status
C67
Protection control status
C68
Compressor stop causes
C69
Time elapsed after compressor stop cause
C70
Protection control causes 1
C71
Protection control causes 2
C72
Protection control causes 3
C73
Compressor error causes 1
C74
Compressor error causes 2
C75
Compressor error causes 3
C80
Counter · Current cut (CM1)
Counter · Current cut (CM2)
C81
C82
Counter · Power transistor overheat (CM1)
C83
Counter · Power transistor overheat (CM2)
C84
Counter · Compressor startup failure (CM1)
C85
Counter · Compressor startup failure (CM2)
Counter · Anomalous compressor by loss of
C86
synchronism (CM1)
Counter · Anomalous compressor by loss of
C87
synchronism (CM2)
Counter · Communication error between inverter
C88
PCB and outdoor control (CM1)
Counter · Communication error between inverter
C89
PCB and outdoor control (CM2)
C90
Counter · Anomalous FMo1
C91
Counter · Anomalous FMo2
C92
Counter · Indoor-outdoor communications error
C93
Counter · CPU reset
Data display
Minimum
range
unit
0~999
10min
-1
10min
-1
0~999
0~100
1%
Only displaying
0~127
1
0~127
1
0~127
See table on P.53
1
0~127
1
See table on P.54
0~255
1h
Displays No. of the protection control of which effect is the strongest
0~127
1
among those occurred from the start of operation after the power on.
Displays No. of the protection control of which effect is stronger secondly
0~127
1
among those occurred from the start of operation after the power on.
Displays No. of the protection control of which effect is stronger thirdly
0~127
1
among those occurred from the start of operation after the power on.
Displays No. of the error detection of which effect is the strongest among
0~127
1
those occurred from the start of operation after the power on.
Displays No. of the error detection of which effect is stronger secondly
0~127
1
among those occurred from the start of operation after the power on.
Displays No. of the error detection of which effect is stronger thirdly
0~127
1
among those occurred from the start of operation after the power on.
1
0~255
EEPROM memory. Resettable.
1
0~255
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
1
0~255
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
1
EEPROM memory. Resettable.
0~255
0~255
1
EEPROM memory. Resettable.
1
0~255
EEPROM memory. Resettable.
1
0~255
EEPROM memory. Resettable.
0~255
1
EEPROM memory. Resettable.
0~255
EEPROM memory. Resettable.
0~255
21
-
51
-
-
-
'14 • KX-SM-202
Remarks