Mitsubishi Heavy Industries FDC280KXZE1 Service Manual page 54

Kxz standard and corrosion protection treatment series vrf inverter multi-system air-conditioners
Table of Contents

Advertisement

Code
Contents of display
No.
C94
Auto back up capable time
C97
Program sub-version
C98
Program POL version
C99
Auto send display
P01
Switching to operation priority
P02
Outdoor fan snow protection control
Outdoor fan snow protection control ON time
P03
setting
P04
Many steps demand setting (1st step demand)
P05
Silent mode setting
P06
CNZ1 function assignment
P07
CNS1 function assignment
P08
CNS2 function assignment
P09
CNG1 function assignment
P10
CNG2 function assignment
Many steps demand setting. (2nd step demand)
P14
P15
Many steps demand setting. (3nd step demand)
P16
Multi-system energy save control II
After changing mode from operation prohibition
P17
mode
Mode unmatched indoor unit setting in forced mode
P18
P19
Pump-down operation by external input
<New superlink setting>
P30
Superlink communication status
P31
Start automatic address setting
P32
Input stating indoor address
P33
Input the number of connected indoor units
P34
Polarity definition
P69
Multi-system energy save control I
Data display
Minimum
range
unit
0~80
1h
0~991
0.00~9.99
0.01
0: (Factory default)
1
0, 1, 2, 3
0: (Factory default)
0 : Invalid
1 : Valid
0, 1
30: (Factory default)
30
Changes to 10, 30, 60, 90 ... 600.
10,30~600(sec)
080: (Factory default)
000,040,060,080
0: (Factory default)
1
0 ~ 3
0: (Factory default)
1
0 ~ 9
0~12
1
Factory setting: 0 (External operation input)
0~12
1
Factory setting: 1 (Demand input)
0~12
1
Factory setting: 2 (Forced cooling/heating input)
0~12
1
Factory setting: 3 (Silent mode input)
080: (Factory default)
000,040,060,080
080: (Factory default)
000,040,060,080
0: (Factory default)
1
0, 1, 2, 3
0: (Factory default)
1
0, 1
0: (Factory default)
1
0, 1
0: (Factory default)
1
0, 1
0: Current Superlink
0, 1
1: New Superlink
0: Automatic address setting standby
1: Automatic address setting start
0: (Factory default)
Specify the starting indoor address connected in one refrigerant system
1
for automatic address setting.
1~127
Specify the number of indoor units connected in one refrigerant system
0: (Factory default)
1
for automatic address setting.
1~24(*)
(*) Maximum connectable number of indoor units for each outdoor unit
0: (Factory default)
0: Network polarity not defined
0, 1
1: Network polarity defined
0: (Factory default)
1
0, 1
52
-
-
'14 • KX-SM-202