2.3 Contents of troubleshooting
(a) List of inspection displays
1)
Indoor and outdoor units
Remote
control
error code
E1
E2
E3
E5
E6
E7
E9
E10
E11
E12
E16
E18
E19
E20
E21
E28
E31
E32
E36
E37
E38
E39
E40
E41 (E51) E41 (E51)-1, 2 Power transistor overheat
E42
E43
E44
E45
E46
E48
E49
E53/E55
E54
E56
E58
E59
E61
E63
7-segment
display
Remote control communication error
Duplicated indoor unit address
Outdoor unit signal line error
Communication error during operation
Indoor heat exchanger temperature thermistor anomaly (ThI-R) Thermistor wire breakage
Indoor return air temperature thermistor anomaly (ThI-A)
Drain trouble
Excessive number of indoor units (more than 17 units) by
controlling one remote control
Address setting error between master and slave indoor units Address setting error
Address setting error by mixed setting method
Indoor fan motor anomaly (FDT, FDTC, FDTW, FDTS,
FDU, FDUM, FDK, FDUT71, FDFW series)
Address setting error of master and slave indoor units
Indoor unit operation check drain motor check mode anomaly Setting error
Indoor fan motor speed anomaly (FDT, FDTC, FDTW,
FDTS, FDU, FDUM, FDK, FDUT71, FDFW series)
Detective panel switch operation (FDT)
Remote control temperature thermistor anomaly (Thc)
E31
Duplicated outdoor unit address No.
E32
Open L3 Phase on power supply at primary side
E36-1, 2
Discharge pipe temperature error (Tho-D1, D2)
Outdoor heat exchanger temperature thermistor (Tho-R)
E37-1, 2
E37-4, 5
and subcooling coil temperature thermistor (Tho-SC, -H)
E37-5, 6
anomaly
E38
Outdoor air temperature thermistor anomaly (Tho-A)
E39-1, 2
Discharge pipe temperature thermistor anomaly (Tho-D1, D2)
E40
High pressure anomaly (63H1-1, 2 activated)
E42-1, 2
Current cut (CM1, 2)
E43-1
Excessive number of indoor units connected, excessive total
E43-2
capacity of connection
E44-1, 2
Liquid flooding anomaly (CM1,2)
Communication error between inverter PCB and outdoor
E45-1, 2
control PCB
E46
Mixed address setting methods coexistent in same network
E48-1
Outdoor DC fan motor anomaly
E48-2
E49
Low pressure anomaly
Suction pipe temperature thermistor anomaly (Tho-S),
E53/E55-1, 2
Under-dome temperature thermistor anomaly (Tho-C1, C2)
E54-1
High pressure sensor anomaly (PSH)
E54-2
Low pressure sensor anomaly (PSL)
E56-1, 2
Power transistor temperature thermistor anomaly (Tho-P1, Tho-P2) Thermistor wire breakage
E58-1, 2
Anomalous compressor by loss of synchronism
E59-1, 2
Compressor startup failure (CM1, 2)
E61-1, 2
Communication error between the master unit and slave units System error
E63
Emergency stop
Name of inspection
68
'14 • KX-SM-202
Classification
Page
Communication error
85
Address setting error
86
Address pairing setting error
87
Communication error
88
89
Thermistor wire breakage
90
System error
91
Communication error
92
93
Address setting error
94
DC fan motor error
95
Address setting error
96
97
DC fan motor error
98
Panel switch error
99
Thermistor wire breakage
100
Address setting error
101
Site setting error
102
System error
103
Thermistor wire
104
breakage
Thermistor wire breakage
105
Thermistor wire breakage
106
System error
107
System error
108
System error
109
Site setting error
110
System error
111
Communication error
112
Address setting error
113
DC fan motor error
114, 115
System error
116
Thermistor wire
117
breakage
Thermistor wire
118
breakage
119
System error
120
System error
121
122
Site setting error
123