Placing The Boiler; Boiler Room Requirements; Recommended Wall Clearances - Buderus Logano G234X Installation And Maintenance Instructions Manual

Gas-fired boiler
Hide thumbs Also See for Logano G234X:
Table of Contents

Advertisement

4

Placing the boiler

4
Placing the boiler
This section explains how to erect and position the boiler
correctly in the boiler room.
4.1

Boiler room requirements

NOTICE: Risk of system damage due to
freezing!
B Install the heating system in a frost-free
room.
WARNING: Damage to the building due to
insufficient load capacity of the floor!
B Before setting the boiler up, check the
load capacity of the floor.
DANGER: Dangers posed by explosive and
easily combustible materials!
B Do not use or store easily-combustible
materials (paper, lace curtains, clothing,
thinners, paints, etc.) near the boiler.
B Maintain a clearance of 16 inches
(415 mm) from the boiler.
NOTICE: Risk of boiler damage from
contaminated combustion air!
B Do not use cleaning agents that contain
chlorine or halogenated hydrocarbons
(e.g. in spray cans, solvents and cleaning
agents, paints, glues).
B Do not store or use these substances in
the boiler room.
B Avoid excessive dust accumulation
(building dust).
10
4.2

Recommended wall clearances

Wherever possible, position the boiler with the
recommended wall clearances. Reducing the minimum
clearances makes the boiler more difficult to access.
The base or foundation on which the boiler is to stand
must be perfectly flat and level. The boiler may be installed
on a flammable base, but not on carpet.
Dimension
Tab. 6 Wall clearances
A space of at least 33 inches (840 mm) is required in front
of the boiler with the door open to allow sufficient
accessibility for operation and maintenance. When the
door is closed, a minimum clearance of 2 inches (50 mm)
is required at the front and sides, a wall clearance of 6
inches (155 mm) is also required for the flue pipe and
30 inches (762 mm) clearance to the ceiling.
Fig. 6
1
Closed door
2
Open door
Logano G234X - Technical specifications are subject to change without prior notice.
Wall clearance
inches (mm)
A
33 (840)
B
6 (155)
C
2 (50)
Where applicable, allow extra wall
clearances for additional components such
as DHW storage tank, pipe connections, flue
silencer or other flue components, etc.
Wall clearances in the boiler room