Specifications; Main Gas Orifice Identification And Rated Orifice Pressure - Buderus Logano G234X Installation And Maintenance Instructions Manual

Gas-fired boiler
Hide thumbs Also See for Logano G234X:
Table of Contents

Advertisement

2
Product description
2.8.2

Specifications

Fig. 3
Pressure drops (1 psi = 69 mbar, 1 GPM = 0.23 m³/h)
x
Flow Rate in GPM ( m³/h)
y
Pressure drops in psi
1
160 500/187 700 BTU/hr (boiler rating 38/45)
2
228 400 BTU/hr (boiler rating 64)
3
266 400 BTU/hr (boiler rating 55)
2.8.3

Main gas orifice identification and rated orifice pressure

Boiler
Number of
capacity
injectors
38
3
45
3
55
4
64
4
Tab. 4 Main gas orifice identification and rated orifice pressure for natural gas
Boiler
Number of
capacity
injectors
38
45
55
64
Tab. 5 Main gas orifice identification and rated orifice pressure for propane gas
8
Main gas orifice
identification
0 - 2000 ft (0 - 610 m)
3.70
3.70
3.50
3.80
Main gas orifice
identification
0 - 2000 ft (0 - 610 m)
3
2.20
3
2.40
4
2.30
4
2.45
Logano G234X - Technical specifications are subject to change without prior notice.
Rated orifice pressure for natural gas
[In. W.C.]
[mbar]
3.0
7.6
4.1
10.4
4.6
11.5
4.4
10.9
Rated orifice pressure for propane gas
[In. W.C.]
10.6
10.5
10.3
10.3
[mbar]
26.5
26.2
25.8
25.9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents