How To Check The Parts - Mitsubishi Electric Mr.Slim PUHZ-RP35VHA3 Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-RP35VHA3:
Table of Contents

Advertisement

11-6. HOW TO CHECK THE PARTS

PUHZ-RP35/50/60/71/100VHA2
PUHZ-RP100/125/140YHA2
PUHZ-RP35/50/60/71/100VHA3
PUHZ-RP100YHA3
Parts name
Thermistor (TH3)
Disconnect the connector then measure the resistance with a tester.
<Outdoor pipe>
(At the ambient temperature 10:~30:)
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heatsink>
Thermistor (TH33)
<Outdoor pipe>
Fan motor(MF1,MF2)
Refer to next page.
Solenoid valve coil
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20:)
<Four-way valve>
(21S4)
Motor for compressor
Measure the resistance between the terminals with a tester.
(Winding temperature 20:)
(MC)
U
V
W
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20:)
(LEV-A/ LEV-B)
For RP35-RP71
Red
M
1
Brown
2
Blue
3
Orange
4
Yellow
5
White
6
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
(LEV-A/ LEV-B)
(Winding temperature 20:)
For RP100-RP140
Gray
M
1
2
Orange
3
Red
4
Yellow
5
Black
6
Measure the resistance between the terminals with a tester.
Solenoid valve coil
(At the ambient temperature 20:)
<Bypass valve>
(SV)
For RP60-RP140
(1)
(1)
Normal
TH4
160k"~410k"
TH3
TH6
4.3k"~9.6k"
TH7
TH33
TH8
39k"~105k"
RP35-71
2350±170"
Red - White
Red - Orange
Gray - Black
Gray - Red
Normal
RP60/71/100/125/140
1197±10"
Check points
Abnormal
Open or short
Normal
RP100/125/140
1435±150"
Normal
Refer to 6-2.
Normal
Brown - Yellow
Brown - Blue
46±4"
Normal
Gray - Yellow
Gray - Orange
46±3"
Abnormal
Open
or
short
67
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short

Hide quick links: