9

WIRING SPECIFICATIONS

9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity
Main switch (Breaker)
Outdoor unit power supply
Outdoor unit power supply earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1.
A breaker with at least 3 mm contact separation in each poles shall be provided. Use earth leakage beaker(NV).
The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.
*2. Refer to 9-3.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device .
Notes: 1. Wiring size must comply with the applicable local and national code. .
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
Single phase
A-Control
Outdoor Unit
Warning:
In case of A-control wiring,
there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
1:1 system

Electrical wiring

Outdoor
unit
Unit
L
power
B
C
N
supply
Indoor/outdoor
unit connection
cable
S1
B Earth leakage breaker
S2
C wiring circuit breaker or
S3
isolating switch
RP35, 50V
~/N (single), 50 Hz,
*1
2 o Min. 1.5
1 o Min. 1.5
3 o 1.5 (Polar)
*2
1 o Min. 1.5
*2
2 o 0.3 (Non-polar)
*3
*4
AC 230 V
*4
AC 230 V
*4
*4
230V
Isolator
S1
S2
S3
Indoor
unit
1
Remote
controller
2
S1
S2
S3
RP60, 71V
~/N (single), 50 Hz,
230 V
230 V
16 A
25 A
2 o Min. 2.5
1 o Min. 2.5
3 o 1.5 (Polar )
1 o Min. 1.5
2 o 0.3 (Non-polar )
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
3 poles isolator
Synchronized twin and triple system Electrical wiring
• Synchronized twin
Unit
power
B
C
supply
B Earth leakage breaker
C wiring circuit breaker or
isolating switch

• Synchronized triple

Unit
power
B
C
supply
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
32
RP100, 125V
RP140V
~/N (single), 50 Hz,
~/N (single), 50 Hz,
230 V
230 V
32 A
40 A
2 o Min. 4
2 o Min. 6
1 o Min. 4
1 o Min. 6
3 o 1.5 (Polar)
3 o 1.5 (Polar)
1 o Min. 1.5
1 o Min. 1.5
2 o 0.3 (Non-polar)
2 o 0.3 (Non-polar)
AC 230 V
AC 230 V
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
S1
A-Control
S2
Indoor Unit
S3
Outdoor
Indoor
unit
unit
L
1
Remote
controller
N
2
Indoor/outdoor
unit connection
cable
S1
S1
S2
S2
S3
S3
Outdoor
Indoor
unit
unit
L
1
Remote
controller
N
2
Indoor/outdoor
connection cable
S1
S1
S2
S2
S3
S3
RP100, 125, 140Y
3N ~ (3phase), 50 Hz,
400 V
16 A
4 o Min. 1.5
1 o Min. 1.5
3 o 1.5 (Polar)
1 o Min. 1.5
2 o 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
Indoor
unit
1
2
S1
S2
S3
Indoor
Indoor
unit
unit
1
1
2
2
S1
S1
S2
S2
S3
S3