Mitsubishi Electric Mr.Slim PUHZ-RP35VHA3 Service Manual page 97

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-RP35VHA3:
Table of Contents

Advertisement

Indication
Outdoor controller board
LED1 (Green) LED2 (Red)
3 blinking 1 blinking
Abnormality of shell thermostat
and discharging temperature (TH4)
Abnormality of superheat due
to low discharge temperature
2 blinking
Abnormal high pressure (High
pressure switch 63H worked.)
3 blinking
Abnormality of outdoor fan
motor rotational speed
Protection from overheat operation(TH3)
Compressor overcurrent
4 blinking
breaking(Start-up locked)
Compressor overcurrent breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
Open/short of discharge thermistor (TH4)
5 blinking
Open/short of outdoor thermistors
(TH3, TH6, TH7 and TH8)
6 blinking
Abnormality of heatsink
temperature
7 blinking
Abnormality of voltage
4 blinking
1 blinking
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
2 blinking
Abnormality of drain sensor (DS)
Float switch(FS) connector open
Indoor drain overflow protection
3 blinking
Freezing (cooling)/overheating
(heating) protection
Abnormality of pipe
4 blinking
temperature
W1 Error code displayed on remote controller
W2 Refer to service manual for indoor unit.
Error
Contents
code
w1
1Check if stop valves are open.
U2
2Check if connectors (TH4, LEV-A, and LEV-B) on outdoor controller
3Check if unit is filled with specified amount of refrigerant.
U7
4Measure resistance values among terminals on indoor valve and
1Check if indoor/outdoor units have a short cycle on their air ducts.
U1
2Check if connector (63H) on outdoor controller board is not disconnected.
3Check if heat exchanger and filter is not dirty.
4Measure resistance values among terminals on linear expansion valve
1Check the outdoor fan motor.
U8
2Check if connector (TH3) on outdoor controller board is disconnected.
Ud
1Check if stop valves are open.
UF
2Check looseness, disconnection, and converse connection of
3Measure resistance values among terminals on compressor using a tester.
UP
4Check if outdoor unit has a short cycle on its air duct.
UH
U6
1Check if connectors(TH3,TH4,TH6 and TH7)on outdoor controller board
U3
U4
2Measure resistance value of outdoor thermistors.
1Check if indoor/outdoor units have a short cycle on their air ducts.
U5
2Measure resistance value of outdoor thermistor(TH8).
1Check looseness, disconnection, and converse connection of
U9
2Measure resistance value among terminals on compressor using a tester.
3Check the continuity of contactor (52C).
4Check if power supply voltage decreases.
5Check the wiring of CN52C.
6Check the wiring of CNAF.
1Check if connectors (CN20, CN21, CN29 and CN44) on indoor
P1
P2
2Measure resistance value of indoor thermistors.
P9
1Check if connector (CN31)(CN4F) on indoor controller board is not
P4
2Measure resistance value of indoor thermistors.
3Measure resistance value among terminals on drain-up machine using
P5
4Check if drain-up machine works.
5Check drain function.
1Check if indoor unit has a short cycle on its air duct.
P6
2Check if heat exchanger and filter is not dirty.
3Measure resistance value on indoor and outdoor fan motors.
4Check if the inside of refrigerant piping is not clogged.
1Check if indoor thermistors(TH2 and TH5) are not disconnected from holder.
P8
2Check if stop valve is open.
3Check converse connection of extension pipe. (on plural units connection)
4Check if indoor/outdoor connecting wire is connected correctly.
Error
Inspection method
board are not disconnected.
outdoor linear expansion valve using a tester.
using a tester.
compressor wiring.
and connector (CN3) on outdoor power board are not disconnected.
compressor wiring.
controller board are not disconnected.
disconnected.
a tester.
(on plural units connection)
97
Detailed
reference
page
P.49
P.50
P.49
P.51
P.51
P.52
P.52
P.50
P.50
P.50
P.50
P.51
W2
W2
W2
W2
W2
W2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents