Sub Cool On Error Occurring Sc; Thermo-On Time Until Error Stops; Indoor Pipe Temperature / Liquid; Indoor Pipe Temperature / Cond./ Eva. - Mitsubishi Electric Mr.Slim PUHZ-RP35VHA3 Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-RP35VHA3:
Table of Contents

Advertisement

SW2 setting
Discharge superheat on error occurring
SHd
0~255
ON
Cooling = TH4-TH6
Heating = TH4-TH5
1
2 3 4 5 6

Sub cool on error occurring SC

0~130
ON
Cooling = TH6-TH3
Heating = TH5-TH2
1
2 3 4 5 6

Thermo-on time until error stops

0~999
ON
1
2 3 4 5 6

Indoor pipe temperature / Liquid

(TH2 (3))
ON
Indoor 3
-39~88
1
2 3 4 5 6

Indoor pipe temperature / Cond./ Eva.

(TH5 (3))
Indoor 3
-39~88
ON
1
2 3 4 5 6
Replacement operation
WIf replacement operation is conducted
ON
even once, "1" is displayed.
If replacement operation time is less
than 2 hrs. "0" is displayed.
1
2 3 4 5 6
U9 Error status during the Error
postponement period
ON
1
2 3 4 5 6
Display detail
105
Explanation for display
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs.
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs.
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs.
-39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
-39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
1: Conducted.
0: Not yet.
Description
Normal
Overvoltage error
Undervoltage error
Input current sensor error
L
-phase open error
1
Abnormal power synchronous signal
PFC error (RP35-71VHA2)
(Overvoltage / Undervoltage / Overcurrent)
PFC/ ACTM error (RP35-140VHA2)
Undervoltage
W Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L
phase open error (04) + PFC error (10) = 14
1
0.5secs.
2 secs.
1
50
0.5secs.
2 secs.
1
15
0.5secs.
2 secs.
4
15
Detection point
Display
00
Power circuit board
01
Controller circuit board
02
Controller circuit board
04
Power circuit board
08
Power circuit board
10
Check CNAF wiring.
20
Defective ACTM/ P.B.
Unit
:
:
Minute
:
:
Code
display