Operation

8
Operation
8.1

BC10 basic controller

The boiler is fitted with a control unit, the BC10 basic controller.
This controller can be used to control the heating system.
▶ Push on the control panel ( fig. 49) to get access to the BC10 basic
controller ( fig. 50).
Fig. 49 Opening the control panel
10
110
100
120
90
130
140
11
1
1
2
Fig. 50 BC10 basic controller
[1]
Main power switch
[2]
"Reset" button
[3]
"Chimney sweep" button
[4]
"Service" button
[5]
Service Tool Connector
[6]
LED "Burner operation"
[7]
LED "Central heat demand"
[8]
Space heating water temperature knob
[9]
Display
[10] DHW temperature knob
[11] LED "DHW demand "
The BC10 basic controller has the following components:
"Main power switch" ( fig. 50, [1])
The main power switch is used to switch the boiler ON and OFF.
"Reset" button ( fig. 50, [2])
If a fault has occurred you may have to restart the boiler by pressing the
"Reset" button.
This is only required in the event of a "locking" fault. "Blocking" faults are
reset automatically as soon as their cause has been corrected.
The display shows [\/r/e| during the reset operation.
30
9
8
130
110
150
90
170
190
7
3
4
5
6
6720645916-47.1N
CAUTION:
▶ Limit the space heating water temperature to the
maximum flow temperature of the floor heating
circuit.
▶ A power interruption discontinues manual
operation. Frost damage may occur.
"Chimney sweep" button ( fig. 50, [3])
The "Chimney sweep" button is used to put the boiler into flue gas test,
service or manual operation mode. The BC10 maximum heating water
temperature setting applies.
• The flue gas test enables the boiler to be run in full-load operation
manually for a short period ( table 12, page 31).
• The service mode enables the boiler to be run in part-load operation
manually for a short period. Measurements and settings can be
carried out on the boiler ( table 13, page 31).
• The manual operation mode enables the boiler to be operated
manually for a longer period. Use this mode when the control system
has not been installed yet or is out of order ( table 14, page 32).
"Service" button ( fig. 50, [4])
The "Service" button is used to display the current space heating water
temperature, the current system pressure etc.
Service Tool connection ( fig. 50, [5])
For further information please contact Buderus.
LED "Burner operation" ( fig. 50, [6])
The LED "Burner operation" lights when the burner of the boiler is active
and is extinguished when the burner is switched OFF.
The LED "Burner operation" indicates the burner status.
LED Status
Explanation
ON
Burner
Boiler water is being heated.
operational
OFF Burner off
The space heating water temperature has reached
the target value and there is no heat demand.
Table 10 Meanings of LED "Burner operation" indications
LED "Central heat demand" ( fig. 50, [7])
The LED "Central heat demand" lights when there is a heat demand and
is extinguished when the heat demand is no longer present.
Space heating water temperature knob ( fig. 50, [8])
The Space heating water temperature knob is used to set the upper
space heating water temperature limit. The unit is °F.
Display ( fig. 50, [9])
The appliance display values, display settings and display codes can be
read out from the display. If a fault occurs the display will immediately
show the accompanying fault code. The fault code flashes if a locking
fault has occurred.
DHW temperature knob ( fig. 50, [10])
The DHW temperature knob is used to select the required temperature
of the hot water in the hot water cylinder. The unit is °F ( table 20,
page 40).
LED "DHW demand" ( fig. 50, [11])
The LED "DHW status" lights when there is a DHW request and is
extinguished when the DHW demand is no longer present.