Check Code List - Toshiba Carrier RAV-SP180AT2-UL Service Manual

Ac split type outdoor unit super digital inverter
Hide thumbs Also See for Carrier RAV-SP180AT2-UL:
Table of Contents

Advertisement

8-2-3. Check Code List (Outdoor)
Sensor lamp part
Remote
controller
Block indication
indication
Operation Timer
Ready
Flash
F04
ALT
Outdoor unit Discharge temp. sensor (TD) error
F06
ALT
Outdoor unit Temp. sensor (TE) error
F08
ALT
Outdoor unit Outside temp. sensor (TO) error
F07
ALT
Outdoor unit Temp. sensor (TL) error
F12
ALT
Outdoor unit Temp. sensor (TS) error
F13
ALT
Outdoor unit Temp. sensor (TH) error
F15
ALT
Outdoor unit Misconnection of temp. sensor (TE, TS)
F31
SIM
Outdoor unit EEPROM error
H01
Outdoor unit Compressor break down
H02
Outdoor unit Compressor lock
H03
Outdoor unit Current detection circuit error
H04
Outdoor unit Case thermostat operation
L10
SIM
Outdoor unit Setting error of service P.C. board type
L29
SIM
Outdoor unit Other outdoor unit error
P03
ALT
Outdoor unit Discharge temp. error
Outdoor unit
P04
ALT
High pressure system error, Power supply voltage error
P05
ALT
Power supply error
P07
ALT
Outdoor unit Heat sink overheat
P15
ALT
Gas leak detection
P20
ALT
Outdoor unit High pressure system error
P22
ALT
Outdoor unit Outdoor fan error
P26
ALT
Outdoor unit Inverter Idc operation
P29
ALT
Outdoor unit Position detection error
No remote controller master unit
E01
Remote controller communication error
E02
Remote controller send error
Regular communication error between indoor and
E03
remote controller
E04
Indoor/Outdoor serial error
E08
Duplicated indoor addresses
E09
Duplicated main remote controllers
E10
Communication error between CPU
Regular communication error between header and
E18
follower indoor units
L03
SIM
Duplicated indoor header units
L07
SIM
There is group cable in individual indoor unit.
L08
SIM
Unset indoor group address
L09
SIM
Unset indoor capacity
P19
ALT
4-way valve inverse error
ALT (Alternate): Alternate flashing when there are two flashing LED
Representative defective position
Detection
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Remote
controller
Remote
controller
Indoor
Indoor
Indoor
Remote
controller
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Outdoor
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Explanation of error contents
Open/Short of discharge temp. sensor was detected.
Open/Short of heat exchanger temp. sensor was detected.
Miswiring between TE sensor and TS sensor
Open/Short of outside temp. sensor was detected.
Open/Short of heat exchanger temp. sensor was detected.
Open/Short of suction temp. sensor was detected.
Open/Short of heat sink temp. sensor (Board installed) was detected.
Misconnection of outdoor heat exchanger temp. sensor and suction temp. sensor was detected.
Outdoor P.C. board part (EEPROM) error was detected.
When reached min-Hz by current release control, short-circuited current (Idc) after
DC excitation was detected.
Compressor lock was detected.
Current detection circuit error
Case thermostat operation was detected.
When outdoor service P.C. board was used, model type select jumper setting was inappropriate.
1) Defective parts on outdoor P.C. board (MCU communication, EEPROM, TH sensor error)
2) When outdoor service P.C. board was used, model type selection was inappropriate.
3) Other error (Heat sink abnormal overheat, gas leak, 4-way valve inverse error) was detected.
Error was detected by discharge temp. release control.
When case thermostat worked or High-pressure SW worked error was detected
by high release control from indoor/outdoor heat exchanger temp. sensor. Power supply voltage error
Power supply voltage error
Abnormal overheat was detected by outdoor heat sink temp. sensor.
Abnormal overheat of discharge temp. or suction temp. was detected.
Error was detected by high release control from indoor/outdoor heat exchanger temp. sensor.
Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit.
Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked.
Position detection error of compressor motor was detected.
Signal was not received from indoor unit.
Main remote controller was not set. (including 2 remote controllers)
Signal cannot be sent to indoor unit.
No communication from remote controller and network adapter
Serial communication error between indoor and outdoor
Same address as yours was detected.
In 2-remote controller control, both were set as master.
(Indoor header unit stops warning and follower unit continues operation.)
MCU communication error between main motor micro computer and micro computer
Regular communication was impossible between master and follower indoor units.
There are multiple header units in a group.
When even one group connection indoor unit exists in individual indoor unit
Indoor address group was unset.
Capacity of indoor unit was unset.
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up ofTE, TS.
: Go on,
: Flash,
: Go off
Automatic
Operation
reset
continuation
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×

Hide quick links:

Advertisement