6. OPTIONS

6.1 EXTENDED RUN-TIME VERSIONS

Extended run-time versions are equipped with additional batteries to increase the autonomy
time of the unit.
These additional batteries are housed in a separate battery cabinet.
Additional batteries will increase the recharging time for the unit.
All other operational information is the same.
If a battery cabinet is connected, the UPS must be informed about the new total battery
capacity to allow a reliable recalculation of the available runtime. Please contact your dealer.
Dependent of the charge condition of the new batteries the new autonomy calculations may
temporarily be unreliable.
Connecting an external charger may cause damage to the UPS. As the batteries are not
galvanically separated from the mains input, the external charger must be galvanically
separated from the mains.
Using an external charger will cause a false autonomy prediction during charging time, the
correct autonomy will be shown 10 hours after reaching battery float charge.
Battery packs can be connected in parallel to increase the autonomy.
All the necessary protection and connection material is included in the delivery.
LP 31
Extension 1
Total capacity
Typical autonomy 100% / 50% load, minutes : 36/78
Number of packs required
Extension 2
Total capacity
(7Ah in LP 31 / 10 kVA)
Autonomia tipica a 100% / 50% load, minutes : 58/120
Number of packs required
Extension 3
Total capacity
(14Ah in LP 31 / 10 kVA)
Typical autonomy 100% / 50% load, minutes : 80/162
Number of packs required
Extension 4
Total capacity
(7Ah in LP 31 / 10 kVA)
Typical autonomy 100% / 50% load, minutes : 101/204
Number of packs required
Extension 5
Total capacity
(14Ah in LP 31 / 10 kVA)
Typical autonomy 100% / 50% load, minutes : 123/256
Number of packs required
* Can be placed in standard UPS cubicle

6.2 SNMP INTERFACE CARD

A plug-in UPS network interface card, making the UPS "SNMP manageable":
it allows communication between UPS and network.
When this option is installed the ComProt communication link is no longer available to the user.
OPM_LPS_31E_8K0_20K_1GB_V010.doc
: 8 kVA
10 kVA
: 7Ah
7Ah
: 14Ah
14Ah
25/58
: *
*
: 14Ah
14Ah
: 21Ah
21Ah
40/92
: 1
1
: 14Ah
14Ah
: 28Ah
28Ah
58/125
: 1
1
: 28Ah
28Ah
: 35Ah
35Ah
78/156
: 2
2
: 28Ah
28Ah
: 42Ah
42Ah
96/188
2
2
35/40
Operating Manual LP 31 / 8-10-15-20 kVA
GE
15 kVA
20 kVA
14Ah
14Ah
28Ah
28Ah
33/75
25/58
1
1
28Ah
28Ah
42Ah
42Ah
55/120
41/96
2
2