INPUT AND OUTPUT
NOT SYNCRONIZED
RUNTIME
LEFT
0:09:41
OUTPUT OFF
NO INPUT POWER
PROG. SHUTDOWN
WITHIN 0:09:17
PROG. SHUTDOWN
LEFT 0:14:03
IMMEDIATE
SHUTDOWN
OPM_LPS_31E_8K0_20K_1GB_V010.doc
The output frequency is not synchronised to the mains (input)
frequency.
The automatic bypass switch is not able to transfer the load
from output converter to bypass and reverse (see chapter
2.5).
This requires synchronisation of the output frequency with
the mains supply frequency.
Synchronisation is only possible if the mains frequency
remains within certain limits (see section 9 - Specifications).
If output converter and mains are not synchronised bypass
operation is inhibited.
If for whatever reason the output converter is not able to
deliver the required output, output power is lost.
The remaining autonomy time.
This figure is counted down during battery operation until
either the mains returns or the batteries are empty.
The output is switched OFF due to a faulty situation, indicated
by the second line, e.g. no input power and depleted batteries.
The output will be switched OFF via ComConnect.
The second line indicates the time until shutdown.
The output is switched OFF via ComConnect.
The second line indicates the time until wake-up.
The wire on connector 18 (rear panel, see figure 6) is
interrupted.
The output is no longer available.
To restart the unit, restore the connection and turn ON/OFF
switch (7) OFF and ON again.
23/40
Operating Manual LP 31 / 8-10-15-20 kVA