Room controller
REV24RF..:
10 / 18
Siemens
Building Technologies
d)
The relay and, as a result, the actuating device must switch at the latest after one minute.
Symbol ▲ is displayed. If not displayed:
• Check actuating device and wiring.
• It is possible that in heating mode the room temperature is higher than the set
temperature setpoint (and lower for cooling mode).
e) Set the temperature setpoint for operating mode "Continuous comfort mode"
desired value.
f) Select the desired operating mode.
User-defined settings:
,
and
simultaneously for 3 seconds:
This resets all temperature and time settings of the program selection slider to default
values (see also "Factory settings" in the operating instructions). The expert settings
remain unchanged.
The clock starts at 12 p.m., the date on 01-01-08 (01 January 2008).
During the reset, all display fields are lit and can be checked accordingly.
All user-defined settings plus expert settings:
Press the DIP switch reset button
seconds:
After the reset, all factor settings are reloaded. This applies to the program selection
slider as well as to the expert settings.
Simultaneously press the "Test and "Learn" buttons on the rear of the REV24RF.. for
1 second. This deletes all data saved from the receivers listed as faulty in Info mode.
After this reset, the REV24RF.. indicates that all faulty receivers were deleted.
Simultaneously press the "Test and "Learn" buttons on the rear of the REV24RF.. for
5 seconds.
This deletes the data saved from all receivers.
After this reset, the REV24RF.. indicates that no more receivers are connected to the room
controller.
Open the RCR10/886 cover. Simultaneously press the "Learn" and override buttons on the
front of the RCR10/868 for 4
LED_1 flashes red. This indicates that no room controller is connected to the receiver.
• Place the room unit in the main living room by considering the following aspects (wall
mounting or free placement using stand).
• The distance to the receiver may not exceed 20 meters or 2 floors.
• Choose the place of installation so that the sensor can capture the air temperature in
the room as accurately as possible without being adversely affected by direct solar
radiation or other heat or cooling sources (about 1.5 meters above the floor for wall
mounting).
Room temperature controller radio set REV24RF../SET
ON
1
2
3
4
5
6
7
8
9
,
seconds
. This deletes the data saved from the room controller.
and
simultaneously for 5
CE1N2206en
24.04.2008
to the

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rev24rfdcRcr10/868

Table of Contents