Function description
Control functions
Example using the settings in the delivered condition
C
60
D
B
50
40
30
30
20
10
A
0
6
00
Time in h
A Start of operation with standard
room temperature
B Set boiler water or flow temperature
in accordance with the selected
heating curve
C Set boiler water or flow temperature
in accordance with coding address
"FA":
50 °C + 20 % = 60 °C

Remote control DIP switches

The DIP switches are located on the PCB in the top part of the casing.
126
(cont.)
7
00
8
00
9
D Duration of operation with raised set
00
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min