Viessmann VITODENS 222-F Installation And Service Instructions Manual page 98

Compact gas condensing boiler 4.8 to 35 kw natural gas and lpg version gc no 47-819-15 (19kw); 47-819-16 (26kw); 47-819-17 (35kw)
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault
Const.
Weath.-
code on
comp.
the dis-
play
F0
X
X
F1
X
X
F2
X
X
F3
X
X
F4
X
X
98
System char-
Cause
acteristics
Burner blocked Internal fault
Burner in a fault
Flue gas tem-
state
perature lim-
iter has
responded.
Burner in a fault
The tempera-
state
ture limiter
has respon-
ded
Burner in a fault
Flame signal
state
is already
present at
burner start
Burner in a fault
No flame sig-
state
nal
Measures
Replace the control
unit.
Check the heating
system fill level.
Vent the system.
Press reset button
R after the flue sys-
tem has cooled
down.
Check the heating
system fill level.
Check the circula-
tion pump. Vent the
system. Check the
temperature limiter
and connecting
cables.
Press reset button
R.
Check the ionisa-
tion electrode and
connecting cable.
Press reset button
R.
Check the ionisa-
tion electrode and
connecting cable,
measure the ioni-
sation current,
check the gas
pressure, check
the gas train, igni-
tion, ignition mod-
ule, ignition elec-
trodes and the con-
densate drain.
Press reset button
R.