Fault codes
(cont.)
Fault
Const.
Weath.-
code on
comp.
the dis-
play
F8
X
X
F9
X
X
FA
X
X
FC
X
X
Fd
X
X
System char-
Cause
acteristics
Burner in a fault
The gas valve
state
closes too
late
Burner in a fault
Fan speed
state
too low during
the burner
start
Burner in a fault
Fan not at
state
standstill
Burner in a fault
Gas train
state
faulty or faulty
modulation
valve control;
or flue gas
path blocked
Burner in a fault
Burner con-
state
trol unit fault
Troubleshooting
Measures
Check the gas
train. Check both
control paths.
Press reset button
R.
Check the fan,
check the fan con-
necting cables and
power supply;
check the fan con-
trol.
Press reset button
R.
Check the fan, fan
connecting cables
and fan control.
Press reset button
R.
Check the gas
train. Check flue
gas system.
Press reset button
R.
Check ignition
electrodes and
connecting cables.
Check whether a
strong interference
(EMC) field exists
near the equip-
ment.
Press reset button
R.
Replace control
unit if the fault per-
sists.