Viessmann VITODENS 222-F Installation And Service Instructions Manual page 69

Compact gas condensing boiler 4.8 to 35 kw natural gas and lpg version gc no 47-819-15 (19kw); 47-819-16 (26kw); 47-819-17 (35kw)
Table of Contents

Advertisement

Heating circuit 1/Heating circuit 2 – Group 5
Coding in the delivered condition
Summer eco function absolute
A6:36
Extended economy func-
tion disabled (only for
weather-compensated
control)
Mixer economy function
A7:0
Without mixer economy
function (only for a
weather-compensated
control unit and heating
circuit with mixer)
Pump idle time change red. mode
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value
changes through a
change in operating
mode or through a
change in the set room
temperature (only for
weather-compensated
control)
(cont.)
Possible change
A6:5
Extended economy control
to
enabled, i.e. the burner and
A6:35
heating circuit pump will be
switched OFF and the
mixer closed at a variable
adjustable value between 5
and 35 °C plus 1 °C. Base
value is the adjusted out-
side temperature. This
value is based on the
actual outside temperature
and a time constant that
takes the cooling down of
an average building into
consideration.
A7:1
With mixer economy func-
tion (extended heating cir-
cuit pump logic):
Heating circuit pump also
"OFF":
■ If the mixer has been
closed for longer than
20 min.
Heating pump "ON":
■ If the mixer changes to
control function
■ If there is a risk of frost
A9:0
Without pump idle time
A9:1
With pump idle time;
to
adjustable from 1 to 15
A9:15
Code 1
69