Extended Performance Ratings - Gree RIO09HP115V1A Technical Product Manual

Ductless mini-split heat pump 9,000– 24,000 btuh
Hide thumbs Also See for RIO09HP115V1A:
Table of Contents

Advertisement

EXTENDED PERFORMANCE RATINGS

Model No: RIO09HP115V1A
Outdoor Ambient
Temperature (DB)
25 F
35 F
45 F
55 F
65F
75F
85F
95F
105F
115F
Outdoor Ambient
Temperature (DB)
(80% RH)
5F
15F
25F
35F
45F
55F
65F
TC- Total Capacity (BtuH)
Capacity data is based on the following conditions:
Cooling Nominal Test Conditions
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
COOLING PERFORMANCE
Indoor Entering Air Temperatures (DB) 50% RH
62 F
TC
SHC
NA
NA
NA
NA
NA
NA
NA
NA
9,569
7,434
9,179
7,176
8,810
7,013
8,370
6,688
7,912
6,436
7,458
6,166
HEATING PERFORMANCE
Indoor Entering Air Temperatures (DB)
65 F
TC
SHC
8,239
8,239
8,926
8,926
9,439
9,439
10,911
10,911
12,357
12,357
13,368
13,368
13,350
13,350
© 2014 Gree Electric Appliance, Inc.
9,000 BtuH 115V
67 F
TC
SHC
NA
NA
NA
NA
NA
NA
NA
NA
10,520
7,985
9,910
7,614
9,445
7,289
9,000
7,191
8,532
6,809
7,911
6,423
70 F
TC
SHC
7,881
7,881
8,239
8,239
9,631
9,631
11,392
11,392
12,243
12,943
13,116
13,116
13,203
13,203
SHC- Sensible Capacity (BtuH)
Heating Normal Test Conditions
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F W
72 F
TC
SHC
NA
NA
NA
NA
NA
NA
NA
NA
11,165
8,152
10,642
7,859
10,266
7,666
9,846
7,394
9,274
7,115
8,450
6,629
75 F
TC
SHC
7,629
7,629
8,231
8,231
9,559
9,559
10,889
10,889
12,386
12,386
12,596
12,596
12,856
12,856
22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents