5.4 Boiler Venting – Side-wall or Direct Vent Systems Sizing Tables & Vent Safety Device
All venting lengt hs must be ca lculated to equivalent lengths,
all application must include at least one 90° elbow
Venting must be a type 'BH" [AL294C® material]
Maximum vent length [equivalent] = 30 ft. [9m]
Minimum vent length [equivalent] 5 ft. [1.5m]
Maximum n umber of 90° elbo ws = 2 o r 3 45° el bows, each
90° e bow is eq uivalent to 10 ft . or straight pip e, the 45°
elbow is equivalent = 5 ft.
Condensate TEE must be provided [equivalent length = 7 ft.]
Appliance reducing adapter [equivalent length 3 ft.]
Sealed combustion, combustion air intake sizing, must be
sized according to the burner manufacturers instructions
Vent [breeching] pressure shall not exceed 0.2 0 inches w .c.
[0.50 mbar]
82274096
Venting
Determining vent length [equivalent] Example:
Appliance reducing adapter
Condensate TEE
12" vent straight vent pipe
E bow 90°
Termination TEE
Length [equivalent] =
GT 220 A Series
Boiler
Model
Connection
ø
GT 224 A
6 inch
GT 225 A
6 inch
GT 226 A
7 inch
GT 227 A
7 inch
GT 228 A
7 inch
Vent termination must be a TEE t
regarding te rmination locations. Do not in
termination TEE length in the vent length calculation.
Venting shall be sloped, so an y condensation developed will
drain through the condensate TEE fitting
Vent safet y devi ce, differential air pressure s witch [manual
reset] NC switch opens on rise of pressure.
Optional function of po wer burners which can emplo y a n
post purge functi on to exh aust flue gases for a fixed time [1
minute to 4 minutes maximum]
Burner employing a standb y air damper closed position, the
closed posit ion should be slight ly o pened to allow hot flu e
gases to escape up
entrapped in the combustion he ad. Important n ote, that in
negative building pressures, the observation and odor of flue
gases may enter the boiler room.
[x1] = 3 ft.
[x1] = 7 ft.
[x3] = 3 ft.
[x1] = 10 ft.
[x1] = 0 ft.
23 ft.
Oil-Gas
[∆p] Pressure switch
Vent ø
Setting [inches w.c.]
4 inch
Set Switch @ 150%
4 inch
above gas burner gas
5 inch
manifold or oil burner
5 inch
head pressure
5 inch
ype, follo w warning
clude the
ward t hrough venting a nd not
11-20-09