Daikin AGZ070EH Installation, Operation And Maintanance Manual page 61

Air-cooled scroll compressor chiller
Table of Contents

Advertisement

Table 44: Pumpdown and System Switch Positions
Switch
ON
Circuits will
PS1, PS2,
operate in the
Pumpdown
normal,
Switches
automatic mode
Unit will operate
S1, System
in the normal
Switch
automatic mode
Post Start-up
After the chiller has been operating for a period of time and
has become stable, check the following:
• Compressor oil level. (Some scroll compressors do not have
oil sight glasses).
• Refrigerant sight glass for flashing.
• Rotation of condenser fans.
• Complete the "Compressorized Equipment Warranty Form."
Shutdown
Temporary Shutdown
Put both circuit switches to the OFF position
1
(Pumpdown and Stop).
After compressors have stopped, put System Switch (S1)
2
to OFF (emergency stop).
IOM 1206-1
Switch Position
OFF
Circuit will go
through the normal
pumpdown cycle
and shut off.
Unit will shut off
immediately without
pumping down
(emergency stop)
Start-up and Shut-down Procedures
Turn off chilled water pump. Chilled water pump to
3
operate while compressors are pumping down.
To start the chiller after a temporary shutdown, follow
4
the start-up instructions.
Extended Shutdown
Front seat both condenser liquid line service valves.
1
Put both circuit switches to the OFF position
2
(Pumpdown and Stop position).
After the compressors have stopped, put System Switch
3
(S1) to the OFF position (emergency stop).
Front seat both refrigerant circuit discharge valves (if
4
applicable).
If chilled water system is not drained, maintain power to
5
the evaporator heater to prevent freezing. Maintain heat
tracing on the chilled water lines.
Drain evaporator and water piping to prevent freezing.
6
If electrical power to the unit is on, the compressor
7
crankcase heaters will keep the liquid refrigerant out of
the compressor oil. This will minimize start-up time
when putting the unit back into service. The evaporator
heater will be able to function.
If electrical power is off, make provisions to power the
8
evaporator heater (if chilled water system is not drained
or is filled with suitable glycol). Tag all opened electrical
disconnect switches to warn against start-up before the
refrigerant valves are in the correct operating position.
To start the chiller after an extended shutdown, follow the
prestart-up and start-up instructions.
61