Daikin AGZ070EH Installation, Operation And Maintanance Manual page 27

Air-cooled scroll compressor chiller
Table of Contents

Advertisement

Setpoints
Setpoints are stored in permanent memory.
Unit Level Setpoints:
Description
Mode/Enabling
Unit Enable
Network Unit Enable
Control source
Available Modes
Network Mode Command
Staging and Capacity Control
Cool LWT 1
Cool LWT 2
Ice LWT
Network Cool Set Point
Network Ice Set Point
Startup Delta T
Shut Down Delta T
Max Pulldown
Nominal Evap Delta T
Demand Limit Enable
Network Capacity Limit
LWT Reset Enable
Configuration
Power Input
Evap Control
Number of Compressors
Expansion Valve Type
Fan VFD enable
Number of fans
Timers
Evap Recirc Timer
Stage Up Delay
Stage Down Delay
Stage Delay Clear
Start-start timer
Stop-start timer
Clear Cycle Timers
Ice Time Delay
Clear Ice Timer
Sensor Offsets
Evap LWT sensor offset
Evap EWT sensor offset
OAT sensor offset
Alarm Settings
Low Evap Pressure Unload
Low Evap Pressure Hold
High Condenser Pressure
High Condenser Pressure Unload
Evaporator Flow Proof
Evaporator Water Freeze
Low OAT Start Time
Low Ambient Lockout
External Alarm Configuration
Clear Alarms
Network Clear Alarms
IOM 1206-1
SetPoint Tables
Setpoints are initially set to the values in the Default
column, and can be adjusted to any value in the Range
column.
Default
Enable
Disable
Local
Cool
Cool
7°C (44.6°F)
7°C (44.6°F)
4.4°C (39.9°F)
7°C (44.6°F)
4.4°C (39.9°F)
5.6°C (10.1°F)
0.3°C (0.5°F)
0.6°C/min (1.1°F/min)
5.6 °C (10.1°F)
Off
100%
Off
Single Point
#1 Only
4
Thermal
No
4
30
240 sec
30 sec
No
15 min
5 min
No
12
No
0°C (0°F)
0°C (0°F)
0°C (0°F)
689.5 KPA(100 PSI)
696.4 KPA(101 PSI)
4240 KPA(615 PSI)
4137 KPA(600 PSI)
5 sec
2.2°C (36°F)
165 sec
0°C (32°F)
Event
Off
Off
Unit Controller Operation
Range
Disable, Enable
Disable, Enable
Local, Network
Cool, Cool w/Glycol, Cool/Ice w/Glycol, Ice, Test
Cool, Ice
See Auto Adjusted Ranges
See Auto Adjusted Ranges
-9.5 to 4.4 °C (14.9 to 39.9 °F)
See Auto Adjusted Ranges
-9.5 to 4.4 °C (14.9 to 39.9 °F)
0.6 to 8.3 °C (1.1 to 14.9 °F)
0.3 to 1.7 °C (0.5 to 3.1 °F)
0.1 to 2.7 °C/min (0.2 to 4.9 °F/min)
3.3 to 8.9 °C (5.9 to 16 °F)
Off, On
0 to 100%
Off, On
Single Point, Multi Point
#1 Only, #2 Only, Auto,
#1 Primary, #2 Primary
4,6
Thermal, Electronic
No, Yes
4,6,8,10,12,14
15 to 300 seconds
120 to 480 sec
20 to 60 sec
No, Yes
10-60 minutes
3-20 minutes
No, yes
1-23 hours
No,Yes
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
-5.0 to 5.0 °C (-9.0 to 9.0 °F)
See Auto Adjusted Ranges
See Auto Adjusted Ranges
3310 to 4275 KPA (480 to 620 PSI)
3241 to 4137 KPA (470 to 600 PSI)
5 to 15 sec
See Auto Adjusted Ranges
150 to 240 sec
See Auto Adjusted Ranges
Event, Alarm
Off, On
Off, On
27