An Example Of A System To Which An Me Remote Controller Is Connected - Mitsubishi Electric PURY-WP200 Service Manual

Table of Contents

Advertisement

[ II Restrictions ]

[6] An Example of a System to which an ME Remote Controller is connected

(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS
Note3
52
TB3
M1M2
TB7
M1M2
S
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OS
Note3
56
TB3
M1M2
TB7
M1M2
S
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2)
No more than 2 ME remote controllers can be connected to a
group of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that
are connected to different outdoor units with each other.
4)
Replace the power jumper connector of the control board from
CN41 to CN40 on only one of the outdoor units.
(not required if power to the transmission line for centralized
control is supplied from a controller with a power-supply func-
tion, such as GB-50ADA)
5)
Provide an electrical path to ground for the S terminal on the ter-
minal block for centralized control on only one of the outdoor
units.
6)
When the number of the connected indoor units is as shown in
the table below, one or more transmission boosters (sold sepa-
rately) are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that
are listed in the specifications for each outdoor unit.)
When the P200 and P250 models are not
included in the connected indoor units
When the P200 and P250 models are in-
cluded in the connected indoor units
HWE1113B
L11
Move the male connector
from CN41 to CN40.
SW2-1 OFF ON
OC
HB
51
53
TB3
TB02
S
M1M2
M1M2
TB7
M1 M2S
To be left
unconnected
To be connected
L21
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OC
HB
55
57
TB3
TB02
M1M2
S
M1M2
TB7
To be left
M1M2
S
unconnected
To be left
unconnected
Note1
System controller
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
A B S
Note2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
Note 3 The figures above show a system to which two outdoor units are connected,
Number of transmission
booster (sold separately)
required
1 unit
2 units
15 - 34
35 - 50
units
units
11 - 26
27 - 42
units
units
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1M2
S
1 2
M1M2
S
A1 B2
A1 B2
101
102
RC
RC
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1M2
S
1 2
M1M2
S
A1 B2
A1 B2
154
104
RC
RC
but only a single outdoor unit can be connected in an HVRF system.
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connec-
tor on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) ME remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
m1 10m [32ft]
m2+m3 10m [32ft]
If the standard-supplied cable must be extended, use a
cable with a diameter of 1.25mm
of the cable that exceeds 10m [32ft] must be included in
the maximum indoor-outdoor transmission line distance
described in (1).
When connected to the terminal block on the Simple re-
mote controller, use cables that meet the following cable
size specifications: 0.75 - 1.25 mm
4) Maximum line distance via outdoor unit
2
(1.25 mm
Same as [5] 4.
3 units
-
43 - 50
units
- 40 -
Interlock operation with the ventilation unit
Group
LC
IC
03
07
TB5
TB15
TB5
1 2
M1M2
S
1 2
M1M2
S
A1 B2
103
RC
Group
LC
IC
06
08
TB5
TB15
TB5
1 2
M1M2
M1M2
S
S
1 2
A1 B2
106
RC
2
[AWG22 to 16])
2
[AWG16]. The section
2
[AWG18-16].
[AWG16] or large)
GB