Mitsubishi Electric PURY-WP200 Service Manual page 45

Table of Contents

Advertisement

[ II Restrictions ]
4. A system in which a system controller is connected to the transmission line for centralized control and which is pow-
ered from an outdoor unit
(1) Sample control wiring
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS
Note 3
52
TB3
M1M2
TB7
M1M2
S
To be left
unconnected
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OS
Note 3
56
TB3
M1M2
TB7
M1M2
S
To be left
unconnected
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a group
of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units.
(not required if power to the transmission line for centralized control
is supplied from a controller with a power-supply function, such as
GB-50ADA)
5)
Short-circuit the shield terminal (S terminal) and the earth terminal (
) on the terminal block for transmission line for centralized control
(TB7) on the outdoor unit whose power jumper connector is mated
with CN40.
6)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
HWE1113B
L11
Move the male connector
from CN41 to CN40.
SW2-1 OFF
OC
HB
51
53
TB3
TB02
S
M1M2
M1M2
TB7
M1M2
S
To be connected
L21
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
OC
HB
55
57
TB3
TB02
M1M2
M1M2
S
TB7
To be left
M1M2
S
unconnected
Note1
System controller
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
A B S
Note2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
Note3 The figures above show a system to which two outdoor units are connected,
L12
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1M2
S
1 2
M1M2
S
1 2
A
B
A
1
2
1
MA
MA
L22
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1M2
S
1 2
M1M2
S
1 2
A
B
1
2
MA
m3
but only a single outdoor unit can be connected in an HVRF system.
When the P200 and P250 models
are not included in the connected
indoor units
When the P200 and P250 models
are included in the connected in-
door units
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connec-
tor on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
L31+L32(L21)
3) MA remote controller wiring
Same as [5] 1.
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L32+L31+L12(L11)
L32+L22(L21)
L12(L11)+L31+L22(L21)
- 36 -
Interlock operation with
the ventilation unit
Group
LC
IC
03
07
TB5
TB15
TB5
M1M2
S
1 2
M1M2
S
B
A
B
2
1
2
MA
Group
LC
IC
06
08
TB5
TB5
TB15
M1M2
M1M2
S
S
1 2
A
B
1
2
MA
Number of transmission booster
(sold separately) required
1 unit
27 - 50 units
21 - 39 units
200m [656ft]
500m [1640ft]
500m [1640ft]
500m[1640ft]
2 units
-
40 - 50 units
GB