Mitsubishi Electric PURY-WP200 Service Manual page 134

Table of Contents

Advertisement

[ VIII Test Run Mode ]
(2) Heating only operation
Model name of HBC controller
Ambient tem-
perature
Operating
Indoor unit
conditions
Piping
Amount of refrigerant
Electric current
Outdoor unit
Voltage
Compressor frequency
Electric current
HBC control-
Voltage
ler unit
Water pump command value [two
units]
HBC control-
LEV opening
ler
High pressure(63HS1)/
Pressure on
Low pressure(63LS)
the refrigerant
side
HBC controller
Outdoor unit
Temp. on the
refrigerant
side
HBC control-
ler
Temp. on the
HBC control-
water side
ler
Indoor unit
HWE1113B
Operation
Indoor
Outdoor
No. of connected units
No. of units in opera-
tion
Model
Fan speed
Main pipe
Branch pipe
Total water pipe length
LEV1
LEV2
LEV3
Discharge TH4
Heat exchanger inlet
TH6
Accumulator inlet TH5
Accumulator outlet
Compressor inlet
Compressor shell bot-
tom
LEV1/LEV2 inlet
Water heat exchanger
outlet TH32/TH33
Inlet
Outlet
PURY-WP200YJM-A
20°C/ -
[68°F/ -]
DB/WB
7°C/ 6°C
[45°F/ 43°F]
5
Unit
5
40/40/40/40/40
-
Hi
5 [17]
m
2.5 [8]
[ft]
12.5 [41]
kg
14.1 [32]
[lbs]
A
8.4
V
400
Hz
53
A
2.83
V
230
100
%
240
Pulse
240
3000
2.40/ 0.69
MPa
[348/ 100]
[psi]
2.37 [344]
70 [158]
1 [34]
0 [32]
-1 [30]
-1 [30]
°C
42 [108]
[°F]
30 [93]
35 [95]
35 [95]
30.7 [87]
- 125 -
Outdoor unit model
PURY-WP250YJM-A
CMB-WP108V-G
20°C/ -
[68°F/ -]
7°C/ 6°C
[45°F/ 43°F]
5
5
50/50/50/50/50
Hi
5 [17]
2.5 [8]
12.5 [41]
15.2 [34]
11.1
400
71
2.83
230
100
210
210
3000
2.50/ 0.67
[363/ 97]
2.47 [358]
73 [163]
1 [34]
-1 [30]
-2 [28]
-2 [28]
41 [106]
34 [86]
38 [100]
38 [100]
32.6 [91]
GB