6.1 Technical specifications

Filter
Output Power @ 120 V
Output Power capacity
@ 120 V
Output Power @ 100 V
AC Input power
l Rated input voltage
l Input voltage range
l input frequency range
Output on battery power
l Voltage
l Frequency
Battery
(sealed lead acid,
maintenance free)
Environnement
l Operating
temperature range
l Storage
temperature range
l Relative humidity
l Noise level
(1) The high and low thresholds can be adjusted using UPS settings.
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 100 V.
For Models 5P 3000, 5P 3000 RT - "CAUTION - To reduce the risk of fire, connect only to a circuit provided
with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric
Code, ANSI/NFPA 70".
For Models 5P 2200, 5P 2200 RT, 5P 1500 RT - "CAUTION - To reduce the risk of fire, connect only to a circuit
provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70".
This product is designed for IT power distribution system.
Page 24
Transformer
Charger
"AVR"
5P 1500 RT
1440 VA
1440 W
1500 VA
1500 W
1200 VA
1200 W
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
4 x 12 V
7.2 Ah
Inverter
Battery
5P 2200
5P 2200 RT
1950 VA
1920 W
2200 VA
1980 W
1330 VA
1300 W
Single phase 100-125 V
80 to 162 V
(1)
100/120 V (-10/+6 %)
50/60 Hz ±0.1 Hz
4 x 12 V
9 Ah
0 to 40 °C
-15 to +50 °C
20 to 90 % (without condensation)
< 45 dBA
5P 3000
5P 3000 RT
3000 VA
2700 W
3000 VA
2700 W
2400 VA
2160 W
(2)
(3)
6 x 12 V
9 Ah
< 50 dBA