Control Specification; Mode Hierarchy - Daikin FLKS25BVMB Service Manual

Inverter pair floor / ceiling suspended dual type b-series
Hide thumbs Also See for FLKS25BVMB:
Table of Contents

Advertisement

SiBE05-311

3. Control Specification

3.1

Mode Hierarchy

Outline
There are two modes; the mode selected in user's place (normal air conditioning mode) and
forced operation mode for installation and providing service.
Detail
1. For heat pump model
2. For cooling only model
Note:
Unless specified otherwise, an indoor dry operation command must be regarded as cooling
operation.
Function and Control
There are following modes; stop, cooling (includes drying), heating (include defrosting)
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Heating
Defrosting
Stop mode (except for cooling/heating modes by indoor command)
Preheat operation
During C (capacitor) is discharging
Stop
There are following models; stop and cooling (including drying).
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Stop mode (except for cooling modes by indoor command)
Preheat operation
During C (capacitor) is discharging
Stop

Control Specification

(R2829)
(R2830)
31