Enclosure Showing Row And Module Positions - Siemens FIREFINDER-XLS Installation, Operation And Maintenance Manual

Hide thumbs Also See for FIREFINDER-XLS:
Table of Contents

Advertisement

CHAPTER 2 |
Outer Door
CAB3-BD
OD-LP
OD-BP
OD-GP
Figure 2-1
Graphic Representation Of CAB3 Enclosure Showing Row And Module Positions
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Inner Door
CAB3-BD
Two
Module
Positions
PMI
One "Row"
Full
"Row"
ID-FP
One
Module
position
ID-SP
8.
Install Field Wiring.
Dress the field wiring that will be going to the CC-5. Strip the insulation
from the wiring, but do not connect the wires to the screw terminals.
9.
Check Field Wiring.
Initiating Devices–Install all initiating device bases and end-of-line devices
where applicable. Install all initiating devices. Refer to the specific installa-
tion instructions provided with each device. Connect the DPU to initiating
devices and test FireFinder-XLS loops. The DPU checks that all of the
devices are communicating and also checks for ground faults and short
circuits. Refer to the DPU User's Manual, P/N 315-033260, for further
information.
Notification Appliances–Install all notification appliances (bells, strobes, etc.)
Refer to the specific installation instructions provided with each device.
10. If the PSC-12 and CC-5/CC-2 were installed on the CAB-MP "OUT" of the
enclosure, mount the complete assembly in the CAB row.
Backbox
CAB3-BB
One "Row"
One
Module
Position
PSC-12/
PSX-12/
ZAM-180
One
Module
Position
CC-2
Two
Module
Positions
CC-5
Each CAB Backbox
"Row" requires a
CAB-MP in order
to mount modules
INSTALLATION
CC-5/CC-2 Cards:
CRC-6
AIC
DLC
DAC-NET
NIC-C
LPB
ZIC-4A
ZAC-40
2-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents