To select All Convenience Page, follow the steps listed below.
1.
Pick up the convenience page microphone.
2.
Depress the All Convenience Page switch.
3.
The All Convenience Page switch, all Speaker Group switch and the Display
Convenience Page switch LEDs flash green.
4.
Depress the key on the convenience page microphone.
5.
All Speaker Group switch LEDs turn steady green indicating that all speaker
groups are now turned on.
6.
The operator can now speak and make the page.
7 .
During the page, the operator can briefly (for up to 5 seconds) unkey and
then re-key the microphone (for example, to cough) - without re-initiating the
pre-announce tone.
8.
To end the convenience page, the operator simply unkeys and replaces the
microphone. The Ready to Page LED turns off.
9.
All Speaker Group switch LEDs turn from steady green to flashing green.
10. To return the system to normal, the operator depresses the All Convenience
Page switch; otherwise, the system will automatically return to normal in
approximately 1-2 minutes and turn off the All Convenience Page and
Speaker Group LEDs.
Select Convenience Page
Select Convenience Page sends the page message from the convenience page
microphone (e.g. external microphone) to selected speaker groups in the system.
Selecting Select Convenience Page cancels Select Background Music.
To select Select Convenience Page, follow the steps listed below.
1.
Pick up the convenience page microphone.
2.
Depress the Select Convenience Page switch. The LED flashes green.
3.
Depress the individual Speaker Group switches.
4.
The selected Speaker Group and Display Convenience Page switch LEDs
flash green.
5.
If no Speaker Group switches are pressed for 120 seconds, the system
automatically returns to normal.
6.
Depress the key on the convenience page microphone.
7 .
The LED on the selected Speaker Group switch turns steady green indicat-
ing that the speaker group is now turned on.
8.
The operator can now speak and make the page to the selected speaker
groups.
9.
During the page, the operator can briefly (for up to 5 seconds) unkey and
then re-key the microphone (for example, to cough) - without re-initiating the
pre-announce tone.
10. To end the convenience page, the operator simply unkeys and replaces the
microphone. The Ready to Page LED turns off.