MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MPC-6000/-7000 panels can also be connected to a computer running terminal emulation
software using an RS232 DB9 serial cable. Terminal emulation software is a communication
program that is designed to emulate various types of text terminals configured to be connected
through a modem or directory over a serial port. HyperTerminal is a terminal emulation
program that is typically bundled with Microsoft
below for wiring connections. Its communication parameters must be as follows:
Baud Rate: 19200
Data Bit:
8
Parity:
None
Stop Bit:
1
Flow Control: None
Following are the pin connections to connect the computer serial connector:
Main Board
Terminal TB4
RX
TX
GND
Figure 2
RS232 Connection for HyperTerminal
RS232 DB9
(computer serial connection)
Pin Number
3 – RXD
2 – TXD
5 – SG
®
Windows operating system. See Figure 2
91