MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

CONTROL UNIT OPERATION

OPERATION INSTRUCTIONS

Standby Condition

In normal standby operation, the green AC POWER ON LED should be illuminated and no
other indicator operating. The display will show the system label and the current date, day, and
time.

Alarm Conditions

 GENERAL ALARM
When a general alarm occurs, all NACs with output type set to "ALARM" activate.
To activate a general alarm, proceed as follows:
 Press "MENU".
 On the MENU display, select "GENERAL ALARM".
 At the next screen, select "Yes".
Silence and reset the system to restore the system to supervisory state.
 NORMAL ALARM
When the system detects an alarm condition, the system alarm LED activates (ON - flashing)
and the buzzer activates (ON - steady). Local audible and visual signals along with remote
alarm signals operate and the LCD panel indicates the alarm.
On receipt of an alarm, proceed in accordance with the established emergency plan. Assure
that all personnel are accounted for, and notify the Fire Department.
To silence the audible after evacuation (where permitted by the codes and control unit
programming), press ALARM SILENCE. The alarm audible will be silenced, the alarm silence
LED will be illuminated.
Operating the ACKNOWLEDGE button will silence the local buzzer and change the LED alarm
indicator from flashing to steady.
 WATERFLOW Alarms
Alarms detected on devices with usage designated as "waterflow" to indicate sprinkler
operation and the audible alarms cannot be silenced in this condition. Operation of alarm
silence will produce no effect.
 SILENCEABLE WATERFLOW Alarms
Alarms detected on devices with usage designated as "waterflow" to indicate sprinkler
operation. The associated audibles are silenceable.
 POSITIVE Alarm Sequence (PAS)
Activation of an initiating device in an input group programmed for PAS, activates the Alarm
LED, display, buzzer, system and user-programmed outputs, but delays additional
programmed outputs for 15 seconds.