MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Wiring Separation and Module Placement

All high voltage and non-power limited wiring must be kept separate from power limited wiring.
A separation of at least a 1/4 inch must be maintained, with high voltage and non-power limited
wiring running in separate conduit openings from power limited wiring.
KNOCKOUTS FOR MPC-6000/MPC7000/RND-2
A
Non-power limited - High Voltage
(AC power) or B
B
Non-power limited - High Voltage
(AC power) or A
C
Power limited
D
Non-power limited
(Battery If external enclosure required)
E
Power limited (non-power limited if MPC-REL is used)
F
Non-power limited if Local Energy Box used
F
Power limited or G or H
G Power limited or F or H
H
Power limited or F or G
SYSTEM MODULES FOR MPC-6000/MPC-7000/RND-2
1. Main Board
2. NPE-1 Transformer
3. MPC-DACT DACT Board or CT-1K City Tie
4. FDLC Loop Driver Board – requires Main Board
or LEM-1 Loop Expansion Board
5. 12603A Network Interface Board
Note: Cannot be used with an expansion module
in the uppermost position.
6. NPE-1 Expansion Transformer
7. NEM-1 NAC Expansion Module
8. LEM-1 Loop Expansion Module
9. HBC-1 Optional Battery Charger
10. Future Expansion
11. NPE-1 Expansion Transformer or
RPT-1 if MPC-REL is installed.
12. 12603A Network Interface
Board or MPC-REL Module.