MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pre-Signal
When an alarm causing device in a Pre-Signal input group is initiated, the alarm condition is
reported at the panel. Its timeout group outputs are not activated until the programmed
investigation delay has elapsed regardless of annunciation of subsequent alarms and
acknowledgement of alarms (see figure below).
Pressing the Reset button at anytime during the Pre-Signal sequence will initiate a reset
condition and restore the panel to stand-by state.
81